Specifications, Trusted, Module t8444 – Rockwell Automation T8444 Trusted TMR Pulse Generator and Monitoring Module User Manual

Page 44

Advertising
background image

Trusted

TM

Module T8444

Issue 09 Apr 10

PD-T8444

44

7. Specifications

System Supply Voltage

20-32Vdc

Circuit Type

Fault tolerant, fully triplicated with optional
line monitoring

Number of Channels

40 Channels

Independent Power Groups

5 each of 8 outputs

Operational Output/Field Voltage Range

18 to 60V dc

Output Voltage

Measurement Range

0 to 60V dc

Maximum Withstanding

-1 to 60V dc

Output Current Rating (Continuous)

0.75A per channel
limited to 6A per power group

Minimum On State Load Current

25mA

Output Off State Resistance (effective
leakage)

33kL

Maximum capacitance

Pre release 3.5: 30-55uF
Release 3.5: at least 2800uF

Output On State resistance

0.6L

Output Short Circuit Protection

Electronic (latching)

Channel to Channel Crosstalk

>-40dB

Output Short Circuit Protection

Automatic

Input Measurement Range

-20 to +28V Limited by A/D range.

Input Impedance

50K ohms

Power Consumption

Field Supply (1A per channel)

System Supply (24V)


24W Dissipated in field device
22W Dissipated in the module

Field Common Isolation

Sustained Working

Maximum Withstanding


±250V dc
±2.5kV dc

Output Turn-on/off Delay

1.0ms

Sample Update Time

1.0ms

Sequence of Events

Event Resolution


1ms

Self-Test Interval

2 minutes

Intrinsic Safety

External barrier

Operating Temperature

-5

°C to 60°C (23°F to 140°F)

Non-operating Temperature

-25

°C to 70°C (-13°F to 158°F)

Temperature change

0.5ºC/min

Operating Humidity

5 – 95% RH non-condensing

Environmental Specifications

Refer to Document 552517

Dimensions

Height

Width

Depth


266mm (10.5ins)
31mm (1.2ins)
303mm (12ins)

Weight

1.285kg (2.8lbs)

Advertising