Rack 5: line_flt, Rack 6: discrep, Rack 7: housekeeping – Rockwell Automation T8444 Trusted TMR Pulse Generator and Monitoring Module User Manual

Page 24: Table 9 rack 5: line_flt descriptions, Table 10 rack 6: discrepancy descriptions, Trusted, Module t8444

Advertising
background image

Trusted

TM

Module T8444

Issue 09 Apr 10

PD-T8444

24

3.2.5. Rack 5: Line_Flt

Channel

Description

1

Field output channel 1 line fault

2

Field output channel 2 line fault

40

Field output channel 40 line fault

Table 9 Rack 5: Line_Flt descriptions

The line fault input state is reported as true (logic ‘1’) for a line fault condition (open circuit, short circuit, and no
field supply voltage). The logic state is the majority voted value.

3.2.6. Rack 6: Discrep

Channel

Description

1

Discrepancy status outputs 1 to 16 (output 1 is LSB)

2

Discrepancy status outputs 17 to 32 (output 17 is LSB)

3

Discrepancy status outputs 33 to 40 (output 33 is LSB)

Table 10 Rack 6: Discrepancy descriptions

Each of the words reports the discrepancy status of 16 output channels. The corresponding bit within the word is
set to ‘1’ when a discrepancy condition is detected on that output channel’s output state (rack 2).

Advertising