4.3. I/O Status LEDs

There are 40 channel status indicators on the module front panel, one for each field input/output.
These indicators are controlled by the FPU. The FPU receives data from each of the module slices.
The FPU performs a 2-oo-3 vote on each data bit from the slices and sets the indicators accordingly.
The input/output status indicator mode is dependent upon the numerical state of the channel. Each
state can be defined to have a particular indicator mode: off, green, red, flashing green, or flashing red.
The configurable indicator modes allow users to customise the status indications to suit individual
application requirements. Without customisation, the default indicator modes are suitable for damper
control installations as described below. Each channel is provided with a Bicolour Led. The channel
LED’s illuminate as follows.

4.3.1. Outputs and Gate Outputs

Function

Off

Green
Steady

Green
Flash

Red
Steady

Red
Flash

Amber
Steady

Amber
Flash

Note

Output off no
faults

Yes

Not
allowed

Not
allowed

Slice LED’s Green

Output Off with
Module Fault

Yes

Not
allowed

Not
allowed

Slice LED’s Red

Output Off with
field Fault

Not
allowed

Not
allowed

Yes

Slice LED’s Green

Output off with
Module and
Field Fault

Not
allowed

Not
allowed

Yes

Slice LED’s Red

Output on No
Faults

Not
allowed

Not
allowed

Yes

Slice LED’s Green

Output On with
Module Fault

Not
allowed

Not
allowed

Yes

Slice LED’s Red

Output On with
Field Fault

Not
allowed

Not
allowed

Yes

Slice LED’s Green

Output on with
Module and
field Fault

Not
allowed

Not
allowed

Yes

Slice LED’s Red

Table 14 Default I/O Status Indicators