Maintenance, Calibration procedure – Rockwell Automation T7480 ICS Regent+Plus Guarded Analog Output Modules User Manual
Page 15
 
Guarded Analog Output Modules (T7480)
 
P D - 7 0 2 6 M a r - 0 6  
15
control logic, you maintain the full resolution of the analog 
output (1 part in 4096) and have a convenient engineering 
range that represents 0.00 to 100.00% (the two decimal places 
are implied). 
Programming Fault Tolerant Guarded Analog Outputs
To program guarded analog outputs in a fault tolerant 
configuration, you should create control logic to calculate the 
value for one of the guarded analog outputs and copy this 
calculated value to the redundant guarded analog output. If 
you use the unscale entry in the analog scaling function block 
you should place this “copy logic” after the analog scaling 
function block in your application program. Figure 9 
illustrates how the Assign instruction in ladder logic can be 
used. 
Figure 9. Programming Fault Tolerant Outputs.
In this example GAO1A is the name of the analog output that 
has been set by your control logic, and GAO1B is the 
redundant analog output. When power flows to the Assign 
element, it reads the value of GAO1A and stores that value to 
GAO1B, so that both of the redundant analog outputs have 
the same value. 
Maintenance
There are no user replaceable parts inside the Guarded 
analog output module. Re-calibration is recommended once 
per year, in order to maintain the rated accuracy of the analog 
output signals over an extended period of time. The following 
procedure describes the equipment and steps necessary to 
calibrate the Guarded analog output module. 
Calibration Procedure
Equipment Required
·
A 5½-digit voltmeter.
·
Six 250 ohm, 0.005%, 5 ppm/
°
C resistors to convert the six
output signals from a current to a voltage.