Rockwell Automation T7480 ICS Regent+Plus Guarded Analog Output Modules User Manual
Page 23
 
Guarded Analog Output Modules (T7480)
 
P D - 7 0 2 6 M a r - 0 6  
23
4. Connect the six termination resistors to the I/O extender
jumper posts as shown in Figure 11. Use test clips as 
required to make the connections. 
5. Remove the four screws on one side of the module and
remove the printed circuit board from the module 
clamshell housing. 
6. With the printed circuit board removed from the system,
check the forward voltage drop (in-circuit) on all 12 output 
diodes with a digital multimeter in the diode test mode (2 
mA current source). Verify that the forward voltage drop 
is within the following tolerances: 
0.6 to 0.8 volts for CR100, CR200, CR300, CR400, CR500, 
and CR600. 
0.2 to 0.45 volts for CR101, CR201, CR301, CR401. CR501 
and CR601. 
7. Check the resistance (in-circuit) of the 12 output diodes
reversely polarized with a digital multimeter set to 20 
MOhm resistance range, by connecting the (+) lead of the 
meter to the cathode and the (-) lead of the meter to the 
anode of the diode. Verify that the resistance is within the 
following tolerances: 
> 20 MOhm for CR100, CR200, CR300, CR400, CR500, 
and CR600. 
> 1 MOhm for CR101, CR201, CR301, CR401. CR501 and 
CR601. 
8. If any of the tests in steps 6 or 7 fails, the board should be
returned to the factory for repair or replacement. If the 
tests passed continue to step 9. 
9. Install the printed circuit board into the I/O extender
module. Perform a voted reset (press two of the processor 
module Reset buttons) and verify that the module is Active 
(green Active LED is on and red Fault LED is off). Allow 
the board to warm up for approximately one minute. 
10. Connect a 47K Ohm, 5% resistor between TP4 (AGND) and
the top lead of the first resistor (10K Ohm) on the SIP 
resistor network RN101 (Figure 12 shows the exact 
location of this resistor). Verify that the module signals a