Fault mode jumper, Important – Rockwell Automation T7480 ICS Regent+Plus Guarded Analog Output Modules User Manual
Page 9
 
Guarded Analog Output Modules (T7480)
 
P D - 7 0 2 6 M a r - 0 6  
9
Each time the single module enters the standby mode all six 
of the output channels are taken off line and the field signals 
become 0 mA. When the module switches back to the control 
mode the field signals return to their controlled values. This 
causes the output loads that have healthy wiring connections 
to experience an output signal that toggles between 0 mA and 
their controlled values which often produces undesirable 
effects. To avoid this, you should monitor the fault status 
system control relay for the output module in your application 
program and use it to set all of the analog output channels to 
zero. Turning all of the outputs off will often be safer than 
letting them toggle between 0 mA and a controlled value. 
Dual Guarded Module Configuration
In a dual module configuration the two modules will switch 
back and forth between control and standby modes. The ON 
status LED will appear to “ping-pong” back and forth between 
the two modules about every one or two seconds. This will 
continue until the open circuit field wiring is corrected. 
During this time the module FAULT status LED will also be 
on for each of the modules and the system will report a fault 
for both modules. 
While in this mode the remaining output loads that have 
healthy field wiring connections should continue to be 
controlled correctly because one of the two modules is always 
in the control mode. 
Fault Mode Jumper
The fault mode jumper is located behind the ID switch cover 
in the lower left-hand corner of each I/O chassis. The position 
of the fault mode jumper determines the module's response to 
system level faults. The fault mode jumper’s position will 
cause all output modules in the I/O chassis to either shutdown 
(set all outputs to zero) or to hold (hold the last state) after a 
system level failure occurs. An example of a system level 
failure is the failure of two processor modules. 
Important!