Guarded Analog Output Modules (T7480)
 
P D - 7 0 2 6 M a r - 0 6  
21
the module must be connected (using the I/O extender) to an 
I/O chassis of an operational Regent system. It is 
recommended that these tests are performed each time that 
you calibrate the Guarded analog output module. 
There are two diodes for each analog output channel that 
must be tested for latent faults. In addition the fault 
summary logic is exercised by injecting a fault. The locations 
of the diodes and other necessary test and measurement 
points for this procedure are shown in Figure 12. 
The I/O extender module has jumper posts that allow you to 
connect the six 250 Ohm termination resistors to the printed 
circuit board plugged into the I/O extender. During the 
calibration steps you will remove any jumpers installed on 
these posts in order to connect the termination resistors to the 
analog outputs. Figure 11 shows the jumper posts to which 
you should connect the resistors for each analog output 
channel.