Figure 4. Fault Tolerant Configuration.
Field Wiring
For field wiring details, refer to PD-7901 - I/O Termination 
Assembly. 
Effects of Open Circuit Field Wiring
When a Guarded analog output module is controlling the 
outputs (as opposed to the standby mode) an open circuit in 
the field wiring connected to a load device will be detected as a 
failure. This causes the controlling module to switch off, 
annunciate a fault and enter the standby mode. Once in the 
standby mode, all of its outputs are shunted to AGND internal 
to the module, thus eliminating the open circuit and the 
module’s comparators become healthy. This will have one of 
two effects based upon single or dual module configuration: 
Single Guarded Module Configuration
In a single guarded output configuration the module will 
toggle back and forth between the controlling and standby 
modes about every one or two seconds. The ON status LED on 
the face of the module will turn on and off repeatedly until the 
open circuit field wiring is corrected. During this time the 
module FAULT status LED will also be on and the system will 
report a fault for this module.