Module operation – Rockwell Automation T7480 ICS Regent+Plus Guarded Analog Output Modules User Manual
Page 2
 
Guarded Analog Output Modules (T7480)
 
2  
Industrial Control Services
Module Operation
A block diagram of the Guarded analog output module is 
shown in Figure 1. 
The processor modules send triplicated write data commands 
over the I/O Safetybus to the Guarded output module. 
Onboard the Guarded output module the triplicated data are 
routed to two independent voter and I/O Safetybus logic 
sections. Each section independently votes the triplicated 
data and drives one digital-to-analog (D/A) converter for each 
of the six output channels. 
Figure 1. Block Diagram of Guarded Analog Output Module.
For each output channel, one of the D/A converter output 
signals is used for the actual analog output drive signal. The 
other D/A converter output signal generates a redundant 
reference output signal. When all circuits are operating 
correctly each channel’s drive output and reference output 
should be the same. These two signals are compared on the 
module and must be the same in order for the module to 
control the field outputs.