Installation and Wiring
EMC Considerations
The DriveGuard Safe Torque Off option and PF40P and PF70 drives may be 
installed in an industrial electromagnetic environment which is consistent 
with the “Second Environment” described in IEC 61800-3 and where the 
EMC requirements documented in the PF40P and PF70 Installation manuals 
have been satisfied. Important installation requirements include:
•
All motor output, control (I/O) and signal wiring for the drive and 
DriveGuard Safe Torque Off option must be shielded cable
•
Grounding (earthing) must conform to the requirements described in the 
drive user manuals
DriveGuard Safe Torque Off Option Installation
PowerFlex 40P Drives
1.
Remove all power to the drive.
ATTENTION: To avoid an electric shock hazard, verify that the voltage on the bus 
capacitors has discharged before performing any work on the drive. Measure the DC bus 
voltage at the +DC and -DC terminals or test points (refer to your drive’s User Manual for 
locations). The voltage must be zero.