Description of Operation

PowerFlex 70 Safe Torque Off Operation

The PowerFlex 70 DriveGuard Safe Torque Off option (see

Figure 9

) disables

the drive’s output IGBT’s by disconnecting the gate control power supply.
When used in combination with a second safety channel (the Enable input),
the system satisfies the requirements of EN ISO 13849-1, Category 3 / PL (d)
for Safe Torque Off and helps protect against restart.

Under normal drive operation, the Safe Torque Off relay is energized, the
enable input is energized, and gate control power is available to the gate
control circuit. If either of these inputs is de-energized, the gate control circuit
is disabled. To meet EN ISO 13849-1, Category 3 / PL (d) operation, both
safety channels must be de-energized. Refer to the following examples for
details.

Figure 9 - PowerFlex 70 Drive Safe Torque Off Circuitry

IMPORTANT

By itself, the Safe Torque Off option initiates a coast-to-stop action. Additional
protective measures will need to be applied when an application requires a change
to the stop action.

+24V DC

PowerFlex 70

AC Drive

Stop

Start

AC Line

Input Power

Common

Enable

M

Gate Control

Power Supply

Gate Control

Circuit

Safety

Channel

Safety

Channel

1

2

3

4

Safe Off Option