Rockwell Automation Publication PFLEX-UM003B-EN-P - July 2012

17

Installation and Wiring

PowerFlex 40P Channel Operation and Verification

PowerFlex 70 Channel Operation and Verification

Safety Function Status Drive In

Safe State

Drive In
Stopped State

Drive In
Stopped State

Drive Able
To Run

Safety Channel Operation

Safe Torque Off Option
Terminals 3 & 4

No Power Applied

Power Applied

No Power Applied

Power Applied

PowerFlex 40P
Enable Input

No Power Applied

No Power Applied

Power Applied

Power Applied

Description For Verification

Safe Torque Off Option
Monitor Contact
Terminals 1 & 2

Closed

Open

Closed

Open

PowerFlex 40P
[Control In Status]
Param. 13, Bit 2

Value = 0

Value = 0

Value = 1

Value = 1

PowerFlex 40P
Comms Status Word
8448, Bit 0

Value = 0

Value = 0

Value = 0

Value = 1

Safe Torque Off
Output

(1)

Relay N.O.
Dig Output States

Closed

Open

Open

Open

(1) Must set A055 [Relay Out Sel], A058 or A061 [Opto Outx Sel] to option 25 “Safe-Off”.

Safety Function Status Drive In

Safe State

Drive In
Stopped State

Drive In

(1)

Stopped State

Drive Able
To Run

Safety Channel Operation

Safe Torque Off Option
Terminals 3 & 4

No Power Applied

Power Applied

No Power Applied

Power Applied

PowerFlex 70
Enable Input

No Power Applied

No Power Applied

Power Applied

Power Applied

Description For Verification

Safe Torque Off Option
Monitor Contact
Terminals 1 & 2

Closed

Open

Closed

Open

PowerFlex 70
Drive Inhibits
Param. 214, Bit 2

Value = 1

Value = 1

Value = 0

Value = 0

(1) A Start/Run command will cause an F111 “Enable Hardware” fault.

PFLEX-UM003.fm Page 17 Wednesday, July 18, 2012 8:26 AM