Description of Operation

Description of Operation

PowerFlex 40P Safe Torque Off Operation

The DriveGuard Safe Torque Off option for PowerFlex 40P (see

Figure 8

)

disables the drive’s output IGBT’s by breaking the link with the drive
microcontroller. When used in combination with a second safety channel (the
Enable input), the system satisfies the requirements of EN ISO 13849-1,
Category 3 / PL (d) for Safe Torque Off and helps protect against restart.

Under normal drive operation, the Safe Torque Off relay is energized, the
enable input is energized, and the drive is able to run. If either inputs is
de-energized, the gate control circuit is disabled. To meet EN ISO 13849-1,
Category 3 / PL (d) operation, both safety channels must be de-energized.
Refer to the following examples for details.

Figure 8 - PowerFlex 40P Drive Safe Torque Off Circuitry

IMPORTANT

By itself, the Safe Torque Off option initiates a coast-to-stop action. Additional
protective measures will need to be applied when an application requires a change
to the stop action.

+24V DC

PowerFlex 40P

AC Drive

Stop

Start

AC Line

Input Power

Common

Enable

M

Gate Control

From Microcontroller

Gate Control

Circuit

Safety

Channel

Safety

Channel

1

2

3

4

Safe Off Option

PFLEX-UM003.fm Page 18 Wednesday, July 18, 2012 8:26 AM