Installation and Wiring

Figure 7 - PowerFlex 70 Safe Torque Off Connector

4.

Tighten screw to 0.8…1.1 N•m (7…10 lb•in).

Wiring

Important points to remember about wiring:

Always use copper wire.

Wire with an insulation rating of 600V or greater is recommended.

Control wires should be separated from power wires by at least 0.3 meters
(1 foot).

DriveGuard Safe Torque Off Option Terminal Block Specifications

Wire Types

Wire Size Range

(1)

(1) Maximum / minimum that the terminal block will accept - these are not recommendations.

Torque

Maximum

Minimum

Maximum

Recommended

1.5 mm

2

(16 AWG)

0.14 mm

2

(26 AWG)

0.25 N•m
(2.2 lb•in)

0.22 N•m
(1.9 lb•in)

Wire Type(s)

Description

Minimum Insulation
Rating

Unshielded

Per US NEC or applicable national or
local code

300V,
60 degrees C
(140 degrees F)

Shielded

Multi-conductor shielded cable such
as Belden 8770(or equiv.)

0.750 mm

2

(18AWG),

3 conductor, shielded.

0.8…1.1 N•m

(7…10 lb•in)

PFLEX-UM003.fm Page 15 Wednesday, July 18, 2012 8:26 AM