General Description

The SIL value for a low demand safety-related system is directly related to
order-of-magnitude ranges of its average probability of failure to satisfactorily
perform its safety function on demand or, simply, average probability of
failure on demand (PFD). The SIL value for a High Demand/Continuous
mode safety-related system is directly related to the probability of a dangerous
failure occurring per hour (PFH).

PFD and PFH Data

These PFD and PFH calculations are based on the equations from Part 6 of
IEC 61508 and show worst-case values.

This table provides data for a 20-year proof test interval and demonstrates the
worst-case effect of various configuration changes on the data.

PowerFlex 40P
PFD and PFH for 20-year Proof Test Interval

PowerFlex 70
PFD and PFH for 20-year Proof Test Interval

Terminology

Attribute

Test Result

PFD

1.74E-05

PFH

2.0E-10

SFF

81%

Attribute

Test Result

PFD

3.4E-05

PFH

3.9E-10

SFF

81%

Abbreviation

Full Term

Definition

PFD

Probability of
Failure on Demand

The average probability of a system to fail to perform its
design function on demand.

PFH

Probability of
Failure per Hour

The probability of a system to have a dangerous failure occur
per hour.

SFF

Safe Failure Fraction The sum of safe failures plus the sum of dangerous detected

failures divided by the sum of all failures.