Overview

64

Banner Engineering Corp.

Minneapolis, U.S.A.

www.bannerengineering.com

Tel: 763.544.3164

EZ-SCREEN

Instruction Manual

Cascadeable EZ-SCREEN

Monitoring Series-Connected Positive-Opening Safety Switches

When monitoring two individually mounted safety switches (as

shown in Figure 7-9), a faulty switch will be detected if it fails

to switch as the guard opens. In this case, the EZ-SCREEN

will de-energize its OSSD output and disable its reset function

until the input requirements are met (i.e., the faulty switch

is replaced). However, when a series of interlocking safety

switches is monitored by the EZ-SCREEN, the failure of one

switch in the system may be masked or not detected at all (refer

to Figure 7-10).
Series-connected, positive-opening interlock switch circuits do

not meet ISO 13849-1 Safety Category 4 and may not meet

Control Reliability requirements because of the potential of

an inappropriate reset or a potential loss of the safety stop

signal. A multiple connection of this type should not be used

in applications where loss of the safety stop signal or an

inappropriate reset could lead to serious injury or death. The

following two scenarios assume two positive-opening safety

switches on each guard:
1. Masking of a failure. If a guard is opened but a switch fails

to open, the redundant safety switch will open and cause the

EZ-SCREEN to de-energize its outputs. If the faulty guard

is then closed, both Cascade input channels also close, but

because one channel did not open, the EZ-SCREEN will not

reset.

However, if the faulty switch is not replaced and a second

“good” guard is cycled (opening and then closing both of

the cascade input channels), the EZ-SCREEN considers the

failure to be corrected. With the input requirements apparently

satisfied, the EZ-SCREEN allows a reset. This system is no

longer redundant and, if the second switch fails, may result in

an unsafe condition (i.e., the accumulation of faults results in

the loss of the safety function).

2. Non-detection of a failure. If a good guard is opened, the

EZ-SCREEN de-energizes its outputs (a normal response).

But if a faulty guard is then opened and closed before the

good guard is re-closed, the failure on the faulty guard is not

detected. This system also is no longer redundant and may

result in a loss of safety if the second safety switch fails to

switch when needed.

The circuits in either scenario do not inherently comply with

the safety standard requirements of detecting single faults and

preventing the next cycle. In multiple-guard systems using series-

connected positive-opening safety switches, it is important to

periodically check the functional integrity of each interlocked

guard individually. Operators, maintenance personnel, and

others associated with the operation of the machine must

be trained to recognize such failures and be instructed to

correct them immediately.
Open and close each guard separately while verifying that the

EZ-SCREEN outputs operate correctly throughout the check

procedure. Follow each gate closure with a manual reset, if

needed. If a contact set fails, the EZ-SCREEN will not enable its

reset function. If the EZ-SCREEN does not reset, a switch may

have failed; that switch must be immediately replaced.
This check must be performed and all faults must be cleared, at

a minimum, during periodic checkouts. If the application can

not exclude these types of failures and such a failure could

result in serious injury or death, then the safety switches

must not be connected in series.

Figure 7-10. Monitoring positive-opening safety switches on multiple gates

WARNING . . .

Not a Safety Category 4 Application

When monitoring multiple guards with a series connection of multiple safety interlock switches,

a single failure may be masked or not detected at all.
When such a configuration is used, procedures must be performed regularly to verify proper

operation of each switch. See “Monitoring Series-Connected Positive-Opening Safety Switches”

(Section 7.9.1) for more information. Failure to do so could result in serious injury or death.

* Standard M12 / Euro-style cables (8-pin male QD)

can also be used, although pin number / wire color

must be verified.

Wh

Open

Bk

Bn

QDE2R4-8..D Cable Pinout*

Pin #1 Brown (Ch 1a) Pin #5 n.c.
Pin #2
Black (Ch 1b)

Pin #6 n.c.

Pin #3 Blue (Ch 2b)

Pin #7 n.c.

Pin #4 n.c.

Pin #8 White (Ch 2a)

Bu

Open

Open