Overview, System operation, 3 reset procedures – Banner EZ-SCREEN Low-Profile Safety Light Curtain Systems User Manual

Page 45

Advertising
background image

P/N 133487

43

Banner Engineering Corp.

Minneapolis, U.S.A.

www.bannerengineering.com • Tel: 763.544.3164

Overview

P/N 140044 rev.

E

43

Banner Engineering Corp.

Minneapolis, U.S.A.

www.bannerengineering.com • Tel: 763.544.3164

EZ-SCREEN LP
Instruction Manual

System Operation

4.3 Reset Procedures

Resetting the System

System resets are typically performed using an external reset

switch. This switch must be located as discussed in Section

3.1.3.
If supervisory control of the reset switch is required, a key

switch may be used, with the key kept in the possession of a

Designated or Qualified Person. Using a key switch will also

provide some level of personal control, since the key may

be removed from the switch. This will hinder a reset while

the key is under the control of an individual, but must not be

relied upon solely to guard against accidental or unauthorized

reset. Spare keys in the possession of others or additional

personnel entering the safeguarded area unnoticed may create

a hazardous situation.

Emitter and Receiver Resets

The EZ-SCREEN LP receiver and emitter each have a Reset

input, pin 8 (Violet wire), that provides for a manual reset input

signal.
The receiver requires a manual reset to clear a Latch condition

and resume operation following a stop command. Internal

Lockout conditions also require a manual reset to return either

the emitter or the receiver to Run mode after the failure has

been corrected. Emitter resets are needed only in the unlikely

event that a Lockout occurs.
Receiver manual resets are required in the following

situations:
Trip output operation – only after a Lockout (see Section 5

for causes).

Latch output operation – at power-up, after each Latch

condition occurs, and after a Lockout.

Reset Routine

To reset the emitter and/or receiver, close the reset switch

for 1/4 to 2 seconds, then open it. (If reset switch model

MGA-KS0-1, listed in Section 2, is used, turn the key 1/4

turn clockwise to close; turn counterclockwise, back to its

original position, to open.) An alternate method to reset either

component is to power the sensor down, then power it up.
NOTE: Closing the reset switch too long will cause the sensor

to ignore the reset request; the switch must be closed

from 1/4 second to 2 seconds, but no longer.

Scan code is used to allow operation of multiple pairs of

emitters and receivers in close proximity (see Sections 3.1.8 and

1.4.4). Scan code may be set to 1 or 2, via DIP switch (see Table

4-1). The scan code setting for each emitter must agree with its

corresponding receiver. Scan code settings may be changed

while in Run mode without causing a Lockout.
Trip or latch output operation is selected on two DIP switches

in the receiver configuration port; see Figure 4-1. Both switches

must be set to the same setting. If they have different settings,

an error code will be displayed.
If the switches are set for trip output (T), the EZ-SCREEN LP will

auto-reset after a blocked condition. If the switches are set for

latch output (L), it will require a manual reset.
External Device Monitoring (EDM): EDM mode is selected

via a 2-position DIP switch on the receiver; see Figure 4-1. For

1-channel monitoring, set the EDM DIP switch to the 1-channel

EDM position. For 2-channel monitoring or no monitoring, set the

switch to the 2-channel EDM position (see Section 3.5.3).
Auxiliary Output: Determines whether the aux. output follows

the state of the OSSDs (ON = Green Status LED) or if the

sensor is in a lockout (ON = Fault).When 2-channel monitoring

(EDM) is selected, these aux. output options are not available

and this DIP switch setting has no effect (see Section 1.4.3).
Reduced Resolution: Enables or disables two-beam reduced

resolution (see Section 3.4.2), and is selected on two DIP

switches that must be set to the same setting.
NOTE: Enabling reduced resolution will affect the minimum

safety distance (see Section 3.1.1).

Inverted Display: Inverts the 7-segment display for right-reading

when sensors are mounted with the indicator end facing up. DIP

switch position OFF results in standard orientation.
Test/Reset: This emitter-only function is used to configure the

violet wire (pin 8) for either a Reset function (similar to the

receiver), or for a Test function which, when activated, simulates

a blocked condition for receiver testing purposes. See emitter

hookups, Figure 3-23.
NOTE: The emitter Test function can not be used in a color-for-

color (“swapable”) hookup.

Fault (Emitter): This emitter-only function is used to determine

whether the emitter Fault signal is active (+24V) when the

emitter locks out. Options are ON or OFF. If the color-for-color

(“swapable”) hookup is used and the receiver is configured for

2-channel EDM or OSSD follow, set this switch to OFF; if the

system is configured for OR fault function, set this switch to ON

(see Figure 3-22).

Advertising