EZ-SCREEN LP

Instruction Manual

Cascadeable EZ-SCREEN

7.7 Configuration for Cascaded Operation

Each cascaded system must be configured, before it can be run

in a production environment.
Before configuration, install all emitters and receivers per

Sections 3 and 7. The last SLPCR-.. receiver must be

terminated either with a terminator plug, or with an EZA-

RBK-1 remote key switch box, or by connecting two closed

mechanical contacts (see Sections 7.8 and 7.9).
Perform the following procedure on the first receiver only in

the cascade (closest to the machine interface). Other than scan

code, set all other receivers in the cascade to the factory default

positions.
1. From either normal operation or a power OFF condition, set

the first and fourth DIP switches (T/L and Red Res) both

to the left (Trip operation and Reduced Resolution enabled

positions). See Figure 7-7.

2. Set the second and third DIP switches (Red Res and T/L)

both to the right (Reduced Resolution OFF and Latch

operation positions).

3. The receiver should be in a lockout condition or power OFF.
4. If power is OFF: Apply power

Lockout condition: Perform a valid reset sequence (close

the reset switch for 0.25 to 2 seconds, then reopen).

5. Coming out of lockout or during startup, the DIP switch

configuration will be recognized as Cascaded Teach Mode,

indicated by the following:

• First receiver display sequentially shows

No E-stop connected: “4C,” “3C,” or “2C”

E-stop w/closed contacts: “4CE,” “3CE,” or “2CE”

E-stop w/open contacts: “4CO,” “3CO” or “2CO”

• Last cascaded receiver display sequentially shows

Terminator connected: “1C”

E-stop w/closed contacts: “1CE”

E-stop w/open contacts: “1CO”

• Other receivers sequentially display “1C”
• All receiver Zone indicators OFF
• All receiver Yellow Reset indicators OFF
• All receiver Status indicators solid red
6. To enable and exit Cascade Teach Mode, reconfigure DIP

switches for normal operation.

7. Perform a valid reset sequence (see Step 4), or cycle power.

7.8 Emergency Stop Buttons and Devices

Cascadeable EZ-SCREEN LP receivers may be connected to one

or more E-stop buttons. The button(s) must connect to the end of

the last receiver in the cascade, in place of the terminator plug.
The connected E-stop button(s) will activate/deactivate the

OSSD outputs in all receivers in the cascade.
The number of E-stop buttons allowed in a series connection is

limited by the total resistance per channel. The total resistance

is the sum of all contact resistance values in the channel, plus

the total wire resistance in the channel. The maximum total

resistance per channel is 100 Ohms.
NOTE: The simultaneity between the two E-stop contacts, on

opening and closing, is 3 seconds. If simultaneity is not

met on either opening or closing, the last receiver’s display

will flash “|-|”. If simultaneity is not met on opening, the

closed contact can be opened later (after more than 3

seconds), then both contacts must be closed again.

Figure 7-7. DIP switch configuration to enable cascade installation

1. Install cascade system per Sections 3 and 7 of

this manual.

With Power ON:
2. On the first receiver only, set the T/L and

Red Res switches as shown (do not change
SCAN or EDM switch positions).

3. Press the Reset button or cycle power.
4. Reconfigure DIP switches for normal operation.
5. Press the Reset button or cycle power.
NO TE: If the EDM wiring does not match the switch

position, an EDM error occurs and cascade
configuration will not be allowed.

WARNING . . .

Emergency Stop Functions

If Cascade Input is used for an Emergency Stop function, do not
mute or bypass the safety outputs (OSSDs) of the EZ-SCREEN LP.
ANSI/NFPA79 and IEC 60204-1 require that the Emergency Stop
function remain active at all times. Muting or bypassing the safety
outputs will render the Emergency Stop function ineffective.