Standard Sinking (NPN) Hookup

Standard Sourcing (PNP) Hookup

Connect dc power to the sensor at
terminals #1 and #2. Power connections
are reverse-polarity protected.

Connect the load between terminals #1
and #4.

Maximum continuous load is 150 mA.

Standard NPN and standard PNP
hookups may be used simultaneously
(maximum load is 150 mA each output).

Connect dc power to the sensor at
terminals #1 and #2. Power connections
are reverse-polarity protected.

Connect the load between terminals #2
and #3.

Maximum continuous load is 150 mA.

Standard NPN and standard PNP
hookups may be used simultaneously
(maximum load is 150 mA each output).

Q85BB62x Series Hookup and Timing Logic Selection

(solid-state output, 10-48V dc)

Alternative Low Saturation Sinking
(NPN) Hookup*

Q85 Series dc Sensors

The output timing logic function (on sensor models with T9 model
number suffix) is selected at the timing logic programming switches,
according to the table (below). The output timing logic delays are set at
the single-turn time adjustment potentiometer. When the timing function
involves more than one time (as in ON and OFF delay, ON-delayed one-
shot, and ON-delayed limit timer functions), the potentiometer sets both
times to the same value between 0.1 and 5 seconds.

Logic function

Switch:

SW1

SW2

SW3

ON and OFF delays (both)

0

0

0

ON delay (only)

0

0

1

OFF delay (only)

0

1

0

No delays

0

1

1

ON delayed one-shot

1

0

0

ON delayed limit timer

1

0

1

One-shot

1

1

0

Limit timer

1

1

1

With the light/dark operate switch (all models) set to light operate (L.O.),
the sensor's outputs are energized when the sensor sees its own modulated
light source (after any ON delay). In the dark operate (D.O.) position,
the outputs are energized when the sensor does not see its modulated light
source (after any ON delay). Sensor sensitivity is set at the single-turn
sensitivity adjustment potentiometer.

Timing Logic Programming
switch detail (T9 models),
see table, left:

Light/dark Operate switch
detail (basic on/off models):

0

1

L.O.

D.O.

SW1

SW2

SW3

This hookup provides direct interfac-
ing to TTL and similar circuits.
Connect dc power at terminals #1 and
#2. Power connections are reverse-
polarity protected.

Connect the load between terminals #1 and
#4. Connect a jumper between terminals
#2 and #5. *In this wiring configuration,
the load hookup is NOT reverse-polarity
protected. Double-check all wiring
before applying power!

Maximum continuous load is 150 mA.

Hookup to dc power and the external load is made at the five screw terminals inside the wiring chamber.
DC power is connected at terminals #1 and #2. The three types of load hookup are diagrammed below.
Maximum continuous load in any hookup is 150 mA (derate per data in Specifications section).
Q8562E emitter hookup: +10 to 30V dc at terminal #1, dc common at terminal #2.