Banner WORLD-BEAM QS30 Water Sensor User Manual

Page 4

Advertising
background image

Step

Remote Line

0.04 seconds < T < 0.8 seconds

Result

Access TEACH Mode/
Learn 1st Condition

• Present 1st condition.
• Single-pulse remote TEACH line.

T

1x

Power LED: OFF
AID LED: Double-flash

Learn 2nd Condition

• Present 2nd condition.
• Single-pulse remote TEACH line.

T

1x

TEACH Accepted
Power LED:
Flashes 3 times, then ON
AID LED: AID mode (flash rate varies depending
upon signal strength)
Sensor returns to RUN mode.

TEACH Not Accepted
Power LED:
OFF
AID LED: Single-flash
Sensor returns to “Learn 1st Condition.”

Restore Factory Default (Maximum Contrast) Setting

Step

Remote Line

0.04 seconds < T < 0.8 seconds

Result

Access TEACH Mode

• Single-pulse remote TEACH line

T

1x

Power LED: OFF
AID LED: Double-flash

Restore Factory Default Setting
(Maximum Contrast Setting)

• Double-pulse remote TEACH line

T

T

T

2x

Power LED: Flashes 3 times, then ON
AID LED: AID mode (flash rate varies depend-
ing upon signal strength)
Sensor returns to RUN mode with maximum
contrast setting.

Analog Output Slope Invert
Teach sensing limits before inverting the output slope.

Step

Remote Line

0.04 seconds < T < 0.8 seconds

Result

Toggle Analog Output Slope

• Triple-pulse remote TEACH line

T

T

T

T

T

3x

Analog output slope toggles between positive
and negative.

WORLD-BEAM QS30H2O Series

4

www.bannerengineering.com - tel: 763-544-3164

P/N 136166 rev. C

Advertising