Adjus t menu – tekmar 545 Thermostat Installation User Manual

Page 11

Advertising
background image

11 of 40

© 2008

D 545 - 07/08

Item Field

Range

Access

Description

0:00 to 2:00 min

(10 sec increments)

Default = 0:30

ADV

FAN DELAY

SECTION

I

Set the fan’s delay time after a heating zone calls for
heat. This allows the fan coil to heat up and prevents
the fan from blowing cold air.
Note: This item is only available when H1 or H2
Terminal is set to Coil or Furnace, Sensor 2 is not
set to Coil and Fan Mode is set to 2.

0:00 to 3:00 min

(10 sec increments)

Default = 0:30

ADV

FAN PURGE SECTION

I

Set how long the fan operates after a call for heating or
cooling ends. This purges any heat or cold remaining
in the fan coil.
Note: This item is only available when H1 or H2
Terminal is set to Coil or Furnace, Sensor 2 is not
set to Duct and Fan Mode is set to 1 or 2.

70 to 160°F, OFF

(21.0 to 71.0°C, OFF)

Default = 110°F

(43.0°C)

ADV

HEAT PURGE FAN

SECTION

I

Set the minimum duct temperature. This purges heat
from the coil after the call for heat is removed.
Note: This item is only available when H1 or H2
Terminal is set to Coil or Furnace, Sensor 2 is set to
Duct and Fan Mode is set to 2.

OFF, 40 to 70°F

(OFF, 4.5 to 21.0°C)

Default = 60°F

(15.5°C)

ADV

COOL PURGE FAN

SECTION

I

Set the maximum duct temperature. This purges cooling
from the coil after the call for cooling is removed.
Note: This item is only available when Cool Stage
is set to 1, Sensor 2 is set to Duct and Fan Mode is
set to 1 or 2.

OFF, 200 to 2000 hr

Default = 500 hr

INST

ADV

FILTER

SECTION

J

Set the number of hours Fan 1 should operate before
you replace the filter. When the time expires, the filter
symbol appears.
Note: This item is only available when the Fan Mode
is set to 1 or 2.

NONE, ZONE, CTRL

Default = CTRL

ADV

WARM WEATHER SHUT DOWN

SECTION R

Set the outdoor temperature at which warm weather
shutdown occurs. Select whether the thermostat
follows the tN4 System Control’s or the zone’s WWSD
for scheduled events.

40 to 100°F, OFF

(4.5 to 38.0°C, OFF)

Default = 72°F

(22.0°C)

INST

ADV

WWSD OCCUPIED AND WAKE

SECTION

R

Set the Warm Weather Shut Down (WWSD) temperature
during Occupied and Wake events.
Note: This item is only available when WWSD is set
to Zone.

Adjust Menu (6 of 7)

Continued on next page.

ADJUS

T MENU