Adjus t menu – tekmar 545 Thermostat Installation User Manual

Page 7

Advertising
background image

7 of 40

© 2008

D 545 - 07/08

Item Field

Range

Access

Description

50 to 100°F

(10.0 to 38.0°C)

LTD

USER

INST

ADV

SET COOL

SECTION

C

Select the cooling room temperature for each event.

Note: At the Limited Access Level, you can only
adjust the temperature +/-3°F (1.5°C) from the last
setting.

Away is only available when Scenes are turned on.

Wake

Default = 78°F (25.5°C)

UnOccupied

Default = 85°F (29.5°C)

Occupied

Default = 78°F (21.0°C)

Sleep

Default = 85°F (29.5°C)

Away

Default = 85°F (29.5°C)

OFF, 40 to 122°F

(OFF, 4.5 to 50.0°C)

LTD

USER

INST

ADV

FLOOR MINIMUM

SECTION

F

Select the minimum floor temperature for each
event.

Note: This item is only available when Sensor 1 or 2
is set to Floor. At the Limited Access Level, you can
only adjust the temperature +/-3°F (1.5°C) from the
last setting.

Wake

Default = 70°F (21.0°C)

UnOccupied

Default = OFF

Occupied

Default = 70°F (21.0°C)

Sleep

Default = OFF

40 to 122°F

(4.5 to 50.0°C)

Default = 85°F

(29.5°C)

ADV

FLOOR MAXIMUM

SECTION

F

Maximum floor temperature.

Note: This item is only available when Sensor 1 or
2 is set to Floor.

OFF, ROOM,

FLOR (Floor),

REM (Remote)

Default = OFF

INST

ADV

SENSOR 1

SECTION A

Select the type of sensor connected to auxiliary
sensor input 1.

OFF, ROOM,

FLOR (Floor),

OUT (Outdoor),

COIL, DUCT

Default = OFF

INST

ADV

SENSOR 2

SECTION A

Select the type of sensor connected to auxiliary
sensor input 2.

OFF, ON

Default = ON

INST

ADV

ROOM SENSOR

SECTION A

Selects whether the built-in room sensor is functional.

Adjust Menu (2 of 7)

ADJUS

T MENU

Continued on next page.