Item Field

Range

Access

Description

40 to 100°F, OFF

(4.5 to 38.0°C, OFF)

Default = 60°F

(15.5°C)

INST

ADV

WWSD UNOCCUPIED AND SLEEP

SECTION

R

Set the Warm Weather Shut Down temperature during
Unoccupied and Sleep events.
Note: This item is only available when WWSD is set
to Zone.

OFF, 35 to 100°F

(OFF, 1.5 to 38.0°C)

Default = OFF

ADV

CWSD OCCUPIED AND WAKE

SECTION

S

Set the Cold Weather Shut Down (CWSD) temperature
for the cooling system during the Occupied and Wake
events.
Note: This item is only available when Cool Stage
is set to 1.

OFF, 35 to 100°F

(OFF, 1.5 to 38.0°C)

Default = OFF

ADV

CWSD UNOCCUPIED AND SLEEP

SECTION

S

Set the Cold Weather Shut Down temperature for
the cooling system during the Unoccupied and Sleep
events.
Note: This item is only available when Cool Stage
is set to 1.

HEAT, COOL,

H/C, OFF

Default = H/C

INST

ADV

OPTIMUM START / STOP

SECTION

M

Select whether to use Optimum Start / Stop for heating,
cooling, or both.
Note: This item is only available when either a heating
schedule and / or a cooling schedule is selected.
Heat can be selected if the heating schedule setting
is on. Cool can be selected if the cooling schedule
setting is on, and Cool Stages is set to 1. To select
H/C, both schedules must be on with Cool Stages
set to 1.

Lo, 2, 3, Hi

Default = Hi

ADV

RADIANT BASE LOAD

SECTION

P

Select the radiant heating load relative to the overall
heating load.
Note: This item is only available when H1 Terminal
is set to HRF1 or HRF2. H2 Terminal is set to Coil,
Convector, Radiator, Baseboard or Other, and Sensor
1 and 2 are not set to FLOR.

Adjust Menu (7 of 7)

ADJUS

T MENU

After the last item, the control returns to the first item in the menu.