View menu, Adjus t menu – tekmar 545 Thermostat Installation User Manual

Page 6

Advertising
background image

© 2008

D 545 - 07/08

6 of 40

Item Field

Range

Access

Description

-58 to 212°F

(-50.0 to 100.0°C)

INST

ADV

DUCT SENSOR

SECTION

A

Current temperature at the duct sensor.
Note: This item is only available when Sensor 2 is
set to Duct.

-22 to 266°F

(-30.0 to 130.0°C)

INST

ADV

SUPPLY TEMPERATURE OF TN4 BUS

SECTION F

Actual water temperature of the tN4 bus for the first
stage of heat.
Note: This item is only available when the thermostat
is connected to an Outdoor Reset Module and the
DIP switch is set to tN4 System Control.

View Menu (2 of 2)

After the last item, the control returns to the first item in the menu.

VIEW MENU

Item Field

Range

Access

Description

YES, NO

Default = NO

USER

INST

ADV

CLEAR FILTER

SECTION J

Indicates when to reset the air filter timer.
Note: This item is only available when Filter is set to
ON, the air filter timer has expired and the Fan Mode
is set to 1 or 2.

OFF, HEAT,

AUTO, COOL

Default = AUTO

USER

INST

ADV

MODE OF OPERATION

SECTION B

Mode of operation of the thermostat or cool group.

40 to 95°F

(4.5 to 35.0°C)

LTD

USER

INST

ADV

SET HEAT

SECTION C

Selected air heating temperature for each event.
Note: At the Limited Access Level, you can only
adjust the temperature +/-3°F (1.5°C) from the last
setting.
Away is only available when Scenes are turned on.

Wake

Default = 70°F (21.0°C)

UnOccupied

Default = 62°F (16.5°C)

Occupied

Default = 70°F (21.0°C)

Sleep

Default = 62°F (16.5°C)

Away

Default = 62°F (16.5°C)

Adjust Menu (1 of 7)

The Adjust Menu items are the programmable settings
used to operate the mechanical equipment.

Continued on next page.

ADJUS

T MENU

Advertising