Error messages (1 of 3) – tekmar 545 Thermostat Installation User Manual

Page 37

Advertising
background image

37 of 40

© 2008

D 545 - 07/08

Error Messages (1 of 3)

Error Message

Description

ADJUST ERROR
The thermostat failed to read the Adjust menu settings from memory and has reloaded
the factory default settings. Operation stops until you check the Adjust menu settings. The
thermostat provides freeze protection only until you check the Adjust menu items.
Note: To clear the error, the access level must be set to Advanced before checking the
settings in the Adjust menu.

MONITOR ERROR
The thermostat failed to read the Monitor menu settings from memory and has reloaded the
factory default settings. The thermostat continues to operate while displaying this error.
Note: To clear the error, the access level must be set to Advanced before checking the
settings in the Monitor menu.

TIME ERROR
The thermostat failed to read the Time menu settings from memory and has reloaded the
factory default settings. The thermostat continues to operate while displaying this error.
Note: To clear the error, the access level must be set to Advanced before checking the
settings in the Time menu.

SCENE ERROR
The thermostat failed to read the Scene menu settings from memory and has reloaded the
factory default settings. The thermostat continues to operate while displaying this error.
Note: To clear the error, the access level must be set to Advanced before checking the
settings in the Scene menu.

SCHEDULE ERROR
The thermostat failed to read the Schedule menu settings from memory and has reloaded the
factory default settings. The thermostat continues to operate while displaying this error.
Note: To clear the error, the access level must be set to Advanced before checking the
settings in the Schedule menu.

MISCELLANEOUS ERROR
The thermostat failed to read the Miscellaneous menu settings from memory and has reloaded
the factory default settings. The thermostat continues to operate while displaying this error.
Note: To clear the error, the access level must be set to Advanced before checking the settings
in the Miscellaneous menu.

tN4 BUS ERROR
Due to a short or open circuit, communication is lost with the tN4 bus. Check wires for damage.
Check ‘C’ and ‘R’ wires for polarity. All devices on the tN4 bus will display this error if there is a
short circuit. If the error is only on this device, check for an open circuit between the thermostat
and Zone Manager. Once the error is corrected press any button to clear the error.

NO tN4 SYSTEM CONTROL
The tN4 System Control DIP switch is set to tN4 System Control and the thermostat does
not detect the tN4 System Control. Once the tN4 System Control is detected, this error will
clear automatically.
Note: If a tN4 System Control is not installed, set the tN4 System Control DIP switch to
None.

ADDRESS ERROR
Two thermostats have been manually set to the same address. The thermostat continues to
operate with this error but does not communicate with the tN4 bus. To clear this error select
an unused address. This can be done automatically by setting the Address item to Auto.

DEVICE LIMIT
You have installed more than 24 devices on the tN4 bus. You must remove the additional
devices and move them to a different bus if possible.