tekmar 545 Thermostat Installation User Manual

Page 38

Advertising
background image

© 2008

D 545 - 07/08

38 of 40

Error Message

Description

DIP SWITCH 2 MODE
The tN4 System Control DIP switch is set to None and the thermostat has detected a tN4
System Control. The thermostat does not operate until this error is corrected. The tN4 System
Control DIP switch must be set to tN4 System Control.

ROOM SENSOR SHORT CIRCUIT
Due to a short circuit, the thermostat failed to read the built-in sensor. If either Sensor 1 or 2 are
set to ROOM, or the thermostat is connected to a tN4 System Control, the thermostat continues
to operate. Otherwise, the thermostat stops operation. To clear the error, press either the
Menu or Item button. If the error does not clear, contact your tekmar sales representative.

ROOM SENSOR OPEN CIRCUIT
Due to an open circuit, the thermostat failed to read the built-in sensor. If either Sensor 1 or 2 are
set to ROOM, or the thermostat is connected to a tN4 System Control, the thermostat continues
to operate. Otherwise, the thermostat stops operation. To clear the error, press either the
Menu or Item button. If the error does not clear, contact your tekmar sales representative.

SENSOR 1 SHORT CIRCUIT
Due to a short circuit, the thermostat failed to read Sensor 1. The thermostat displays the

error and continues to operate unless:
No other Room sensors are available and the thermostat is not connected to a tN4 System

control. Then the thermostat stops operation.
No other Floor sensors are available and the Floor Maximum is not set to Off, then the H1

contact no longer operates.
Locate and repair the problem as described in the Data Brochure D 070. Once the error is

corrected, press any button to clear the error.

SENSOR 1 OPEN CIRCUIT
Due to an open circuit, the thermostat failed to read Sensor 1. The thermostat displays the

error and continues to operate unless:
No other Room sensors are available and the thermostat is not connected to a tN4 System

control. Then the thermostat stops operation.
No other Floor sensors are available and the Floor Maximum is not set to Off, then the H1

contact no longer operates.
Locate and repair the problem as described in the Data Brochure D 070. Once the error is

corrected, press any button to clear the error.

SENSOR 2 SHORT CIRCUIT
Due to a short circuit, the thermostat failed to read Sensor 2. The thermostat displays the

error and continues to operate unless:
No other Room sensors are available and the thermostat is not connected to a tN4 System

control. Then the thermostat stops operation.
No other Floor sensors are available and the Floor Maximum is not set to Off, then the H1

contact no longer operates.
Locate and repair the problem as described in the Data Brochure D 070. Once the error is

corrected, press any button to clear the error.

SENSOR 2 OPEN CIRCUIT
Due to an open circuit, the thermostat failed to read Sensor 2. The thermostat displays the

error and continues to operate unless:
No other Room sensors are available and the thermostat is not connected to a tN4 System

control. Then the thermostat stops operation.
No other Floor sensors are available and the Floor Maximum is not set to Off, then the H1

contact no longer operates.
Locate and repair the problem as described in the Data Brochure D 070. Once the error is

corrected, press any button to clear the error.

Error Messages (2 of 3)