Cdv series direct vent gas fireplace, Mantels, Clearance to combustibles – Vermont Casting 36CDVRRN User Manual

Page 6: Locating your fireplace

Advertising
background image

6

CDV Series Direct Vent Gas Fireplace

20010175

Top of Unit to Ceiling ............................... 36” (914 mm)
Front of Unit to Combustibles .................. 36” (914 mm)
Appliance

Top .......................................................... 0” (0 mm)

Bottom ..................................................... 0” (0 mm)

Side ......................................................... 0” (0 mm)

Back ........................................................ 0” (0 mm)

Venting
Concentric sections of DV Vent

Top, bottom & sides .............................. 1” (25 mm)

NOTE: Hood must be permanently installed with
three (3) sheet metal screws supplied in fireplace.

Mantels

The height that a combustible mantel is fitted above the
fireplace is dependent on the depth of the mantel. This
also applies to the distance between the mantel leg (if
fitted) and the fireplace.
For the correct mounting height and widths refer to
Figs. 3a and 3b, and the following Mantel Charts.
The fitting of a bay window trim kit does not effect
the distances and reference points referred to in the
diagram and chart.
Noncombustible mantels and legs may be installed at
any height and width around the appliance.
When using paint or lacquer to finish the mantel, such
paint or lacquer must be heat resistant to prevent
discoloration.

Clearance to Combustibles

CFM170

J

F

G

H

I

Mantel

Leg

CFM164a

Mantel Leg Chart

06/22/01 sta

Black

Surround

Face

CFM170

DV Builder Front

View

O

N

M

L

K

Side of

Combustion Chamber

CFM164a

Mantel

Mantel Leg FromSide

Ref.

Leg Depth

Ref.

of Comb. Opening

F

10” (254 mm)

K

11¹⁄₂” (292 mm)

G

8” (203 mm)

L

9¹⁄₂”

(241 mm)

H

6” (152 mm)

M

7¹⁄₂”

(191 mm)

I

4” (101 mm)

N

5¹⁄₂”

(140 mm)

J

2” (51 mm)

O

3¹⁄₂”

(89 mm)

Fig. 3b Combustible mantel leg minimum installation.

CFM146

A B C D E

V

W

X

Y

Z

Fireplace

CFM146

DV Mantel Chart

7/5/01 sta

Hood

Top of Combustion

Chamber

Mantel Chart

Mantel Shelf or

Mantel from Top of

Ref. Breast Plate Depth Ref. Combustion Chamber
V

10” (254 mm)

A

17” (432 mm)

W

8” (203 mm)

B

15” (381 mm)

X

6” (152 mm)

C

13” (330 mm)

Y

4” (101 mm)

D

11” (279 mm)

Z

2” (51 mm)

E

9” (229 mm)

Fig. 3a Combustible mantel minimum installation.

Standoff

Finish Wall

Noncombustible

Material

A) Flat on wall

B) Cross corner

C) **Island

D) Room divider

E) Flat on wall corner

F) Chase installation

Y) Refer to “Clearance to Combustibles” Section

NOTE: (Fig. 1)
** Island (C) and Room Divider (D) installation is possible as
long as the horizontal portion of the vent system (X) does not
exceed 20’ (6 m) with a minimum vertical of 4’ (122 cm). See
details in Venting Section.

Locating Your Fireplace

Y

E

A

B

C

D

F

Y

B

X

LU584-R

Locating unit

2/23/01 sta

X

LU584-R

Fig. 1 Locate gas fireplace.