SECTION 3: INSTALLATION

3.01 Installation Requirements

Electric Supply

The electrical supply network, the gas and water supply system must meet local safety standards. This

conformity shall be checked by qualified personnel.

Ultra-Cut 100 XT™ Power Supply

Input

Power Input

Current

Suggested Sizes (See Note)

Voltage

Freq.

3-Ph

3-Ph

Fuse (Amps) Wire (AWG)

Wire (mm

2

)

(Volts)

(Hz)

(kVA)

(Amps)

3-Ph

3-Ph

3-Ph

380

50/60

21

33

40-45

#12

4

Ultra-Cut 200 XT™ Power Supply

Input

Power Input

Current

Suggested Sizes (See Note)

Voltage

Freq.

3-Ph

3-Ph

Fuse (Amps)

Wire (AWG) Wire (mm

2

)

(Volts)

(Hz)

(kVA)

(Amps)

3-Ph

3-Ph

3-Ph

380

50/60

42

65

100

#6

16

Ultra-Cut 300 XT™ Power Supply

Input

Power Input

Current

Suggested Sizes (See Note)

Voltage

Freq.

3-Ph

3-Ph

Fuse (Amps) Wire (AWG) Wire (mm

2

)

(Volts)

(Hz)

(kVA)

(Amps)

3-Ph

3-Ph

3-Ph

380

50/60

63

97

150

#4

25

IEC

380

50/60

71

110

150

#4

25

Ultra-Cut 400 XT™ Power Supply

Input

Power Input Current

Suggested Sizes (See Note)

Voltage

Freq.

3-Ph

3-Ph

Fuse (Amps)

Wire (AWG) Wire (mm

2

)

(Volts)

(Hz)

(kVA)

(Amps)

3-Ph

3-Ph

3-Ph

380

50/60

93

144

200

#1

50

NOTE

* Suggested wire size based on United States NFPA 70 National Electrical Code 2011 edition pub-

lished by the National Fire Prevention Association. Listings are from table 400.5(A)(2) for flexible cord

of certain types rated for 75 deg C in ambient temperatures up to 30 deg C. Using wires of lower

temperature rating or different insulation type may require larger wire size. Derate for higher ambient.

These are suggestions only. Always refer to your local and national codes that apply to your region for

final determination of correct wire type and size.