You must connect the router chassis to a reliable earth ground. The ground wire must be installed in
accordance with local electrical safety standards.

For NEBS-compliant grounding, use size AWG 6 (13 mm

2

) wire and the two-hole barrel lug

provided in the router accessory kit.

For NEC-compliant grounding, use size AWG 14 (2 mm

2

) or larger wire and an appropriate

user-supplied ring terminal.

For EN/IEC 60950-compliant grounding, use size AWG 18 (1 mm

2

) or larger wire and an

appropriate user-supplied ring terminal.

To connect the router to a reliable earth ground, follow these steps:

Step 1

Strip one end of the ground wire to the length required for the two-hole barrel lug or terminal.

For the NEBS two-hole barrel lug, approximately 0.75 in. (20 mm)

For a user-provided ring terminal, as required

Step 2

Crimp the ground wire to the two-hole barrel lug or ring terminal, using a crimping tool of the
appropriate size.

Step 3

Attach the two-hole barrel lug or ring terminal to the router chassis as shown in

Figure 8

,

Figure 9

,

Figure 10

, or

Figure 11

. For a two-hole barrel lug, use the two screws with captive locking washers

provided. For a ring terminal, use one of the screws provided. Tighten the screws to a torque of 8 to 10
in-lb (0.9 to 1.1 N-m).

Step 4

Connect the other end of the ground wire to a suitable grounding point at your site.

Figure 8

NEBS-Compliant Two-Hole Barrel Lug Ground Connection on Cisco 3825 Router

117015

EN

NMD-

ESW-

36

23x

5x

FastEthernet Ports

22x

4x

21x 3x

20x

2x

19x

1x

18x

0x

29x 11x

28x 10x

27x 9x

26x

8x

25x

17

24x

6x

35x 17x

34x 16x

33x 15x

32x 14x

31x 13x

30x 12x

Ext

Pwr

-48V

0x

18x

GE0

10/100/

1000

Base-Tx

35x

10/100/100

0

Base-Tx

GE1

17x

Ground lug
attachment

Advertising