Connecting routers to ac power, Connecting routers to dc power – Cisco 3800 Series User Manual

Page 50

Advertising
background image

Power Connections

20

Connecting Cables to Cisco 3800 Series Routers

OL-5970-02

Connecting Routers to AC Power

If your router uses AC power, connect it to a 15 A, 120 VAC (or 10 A, 240 VAC) circuit with overcurrent
protection. If backup power is required, see the

“Connecting Routers to Backup Power” section on

page 27

.

Note

The input voltage tolerance limits for AC power are 85 and 264 VAC.

Warning

AC connected units must have a permanent ground connection in addition to the power cable ground
wire. NEBS-compliant grounding satisfies this requirement.
Statement 284

Warning

This product requires short-circuit (overcurrent) protection, to be provided as part of the building
installation. Install only in accordance with national and local wiring regulations.
Statement 1045

The following warning applies to both AC power supplies and AC power supplies with IP phone power
in the Cisco 3825 router:

Warning

This product relies on the building’s installation for short-circuit (overcurrent) protection. Ensure that
the protective device is rated not greater than:
120 VAC, 45 A (240 VAC, 30 A).
Statement 1005

The following warning applies to both AC power supplies and AC power supplies with IP phone power
in the Cisco 3845 router:

Warning

This product relies on the building’s installation for short-circuit (overcurrent) protection. Ensure that
the protective device is rated not greater than:
120 VAC, 30 A (240 VAC, 20 A).
Statement 1005

Connecting Routers to DC Power

If your router has a DC-input power supply, follow the directions in this section for proper wiring. If
backup power is required, see the

“Connecting Routers to Backup Power” section on page 27

.

DC Wiring Requirements for Cisco 3800 Series Routers

Warning

Use copper conductors only. Statement 1025

Warning

This product requires short-circuit (overcurrent) protection, to be provided as part of the building
installation. Install only in accordance with national and local wiring regulations.
Statement 1045