Caution – Viking Pump TSM750: M10 Power Load Monitor User Manual
Page 6
PARAMETER
VALUE
FACTORY
SETTING
NOTE
RATED POWER
0 1 2 4 8 16 32 64
64
See Table 3
RELAY INVERTED
0(no) 1(yes)
0
0=Relay Activated
alarm
ALARM CURRENT= 0
0(no) 1(yes)
0
Alarm at no motor
current
MAX OR MIN
0(MIN) 1(MAX)
1
0=underload
1=overload
RESPONSE DELAY
0 1 2 4 8 16 32 64
2
Response delay in
seconds (0=50ms)
START DELAY
0 1 2 4 8 16 32 64
2
Start delay in seconds
MARGIN
(% of rated power)
0 1 2 4 8 16 32 64
8
Load change for alarm
sensitivity. Fig 6
AUTO SET
Autoset load level
is automatically set
if VAL key is
pressed for 3
seconds
VAL key must be
pressed when LED
parameter AUTOSET
is lit. LED bar is
switched off when
Autoset level is set.
SETTING
RATED MOTOR POWER IN HP
OR Kw
0
0 – 0.5
1
0.51 - 1.5
2
1.51 - 2.5
4
2.51 - 6
8
6.1 - 12
16
12.1 - 24
32
24.1 - 48
64
48.1 - 75
FIGURE 6
Alarm Level and Margin
Hints!
Change the load on the machine to find out if
appropriate load limit margin is set correctly. You can
also reduce the margin by one or more steps to find
out at what level the machine will trip. See figure 6.
Set/Reset e.g. start delay, response delay, trip margin
etc. if necessary (see table 2).
If the alarm level is difficult to set - simply perform an
Auto Set when the motor is stopped. Then start the
machine, run at normal load and perform an Auto Set
again.
If a wrong value is unintentionally set - simply set a
new value. If the value is not confirmed by pressing
PAR, the new value is not accepted (time out after 30
seconds
).
SECTION TSM 750
ISSUE A
PAGE 5 OF 7
Pump with overload protection, motor 11 kW (fig. 6).
1. Check output power on motor plate and see table 3
(11 kW =Rated Motor Power 6.1- 12) -setting 8.
2. Switch on the supply voltage - Power LED green.
3. Press
PAR once - “LED” AUTO SET turns green.
4. Keep pressing
PAR until RATED POWER is
selected.
5. Press
VAL - Value “64” flashes (factory setting).
6. Set recommended value according to table 3. Keep
pressing
VAL until chosen value (8) flashes.
7. Confirm chosen value by pressing
PAR.
8. Press
PAR again and select MAX.
9. Press
VAL . Choose the factory setting MAX -
Overload Protection – “1”.
10. Confirm chosen value (1) by pressing
PAR.
11. Press
PAR again and select RELAY INVERTED.
12. Press
VAL. Choose the factory setting “no” =“0”.
13. Confirm chosen value (0) by pressing
PAR.
The above parameters are necessary to set for safe
functioning. Note that “Rated Power” for the motor must be
set before Auto Set.
EXAMPLE: PUMP WITH OVERLOAD
PROTECTION
CAUTION!
Positive displacement pumps require some form of
over-pressure protection to be placed in the discharge
line in conjunction with the Power Load Monitor.
Pressure spikes created by sudden discharge line
blockage may cause serious pump damage.
TABLE 2
Parameters and Values
TABLE 3
Setting or Rated Motor Power