Technical data, Parameter list terminals, Viking pump, inc. ● a unit of idex corporation – Viking Pump TSM750: M10 Power Load Monitor User Manual
Page 7
PARAMETER FACTORY
SETTING
ACTUAL
SETTING
ALTERNATE
SETTING
Rated Power
64
Relay Inverted
0
Alarm Current = 0
0
Max or Min
1
Response Delay
2
Start Delay
2
Margin 8
TERMINAL LABEL
FUNCTION
1 S1
Current transformer input for CTM 010,
CTM 025,CTM 050
1
2 S2
Current transformer input
1
3
4
5 RES
Reset input. Latched or unlatched alarm
is selected via this input.
6 C
Alarm relay common and also reset
common
7 NC
Alarm relay is normally closed.
8 NO
Alarm relay is normally open.
9 L1
Motor voltage phase L1
10
11 L2
Motor voltage phase L2 ( N for single
phase motors)
2
12
13 L3
Motor voltage phase L3 (N for single
phase motors)
2
1 Note Terminals 1 and 2 (S1, S2) carry Line voltage
2 N Must be connected to terminal 11 and 13 (single phase)
PAGE 6 OF 7
ISSUE A
SECTION TSM 750
Dimensions
(WxHxD)
1.77” x 3.54”x4.53 “ (45x90x115mm)
Mounting
35mm DIN-rail 46277
Weight
5.65 oz. (175g)
Supply Voltage
1x100-240 (±10%)
3x100-600 (±10%)
3x600-690 (±10%)
Frequency
50 or 60 Hz
Current Input
Current Transformer CTM 010,025, or 050
(max 50 A motor)
Power Consumption
Max 3 W
Start-up Delay
1-64 seconds
Response Delay
0.05–64 seconds
Relay Output
5 A/240 VAC Resistive, 1.5 A/240 VAC Pilot Duty/AC12
Fuse
Max 10 A
Terminal Wire Size
Use 75° C copper (CU) wire only.
0.2-4.0 mm
2
single core (AWG12)
0.2-2.5 mm
2
flexible core (AWG14)
Strip length 0.32” (8mm)
Terminal Tightening
Torque
5-7 lb-in (0.56-0.79 Nm)
Repeatability
± 2.5% FS, 24H @ 77°F (25°C)
Temperature Tolerance
<0.1%/ °C
External RESET on
Terminal 5
Max 240VAC or 48 VDC
High :> 24VAC/DC Low: < 1VAC/DC
Operating Temperature
4-122°F (-20-+50°C)
Storage Temperature
22-176°F (-30-+80°C)
Protection Class
IP20
Approved To
CE, cUL (UL up to 600V)
PARAMETER LIST
TERMINALS
TECHNICAL DATA
VIKING PUMP, INC. ● A Unit of IDEX Corporation ●
Cedar Falls, IA 50613 USA ©2002
SECTION TSM 750
ISSUE
B