Cooper Instruments & Systems DFI Infinity CS Economy Digital Indicator User Manual

Page 19

Advertising
background image

DFI INFINITY CS (V- M3598/N/0906)

16

CF 70

4.3.2 Scaling without Known Loads

To scale without known inputs, calculate input values based on transducer specifications and manually enter them
via the front-panel push buttons. The following example assumes load cells with these specifications:
Maximum

Load:

100.0

lbs

Output:

3.1

mV/V

Sensor Excitation:

10 Vdc

Output:

31 mV = (3.1 mV/V) x (10 V)


1. Determine the correct values for

and

, based on the load cell specifications. In most cases,

&

are equal to the minimum and maximum of the transducer output span. The example assumes

&

are equal to the range of the load

= 0 and

= 100.0). Calculate

and

using the

load cell output span and the following equation:

= (Sensor Output) x (Natural Gain) x (Multiplier).

Table 4-3 Natural Gain

Input range

Span units

Natural gain

0 to 100 mV

Millivolts

100 cts/mV

±50 mV

Millivolts

40 cts/mV

0 to 10 V

Volts

1000 cts/V

±5 V

Volts

400 cts/V

0 to 20 mA

Milliamps

500 cts/mA


2. Determine the multiplier by the Input Resolution setting (

in the

menu) and the input range selected.

Typically

is suitable for most applications.

Table 4-4 Input Resolution Multiplier









3. Determine

and

input range and resolution. The example selects the 0 to 100 mV range and 10 uV

resolution (

).

Example:

= (0 mV) x (100 cts/mV) x (1.000) =0

= (31 mV) x (100 cts/mV) x (1.000) = 3100

= 0000

= 100.0

4. Press

MENU button until the meter shows

.

5. Press

the

X/TARE button. The meter shows

.

6. Press

the

X/TARE button again. The meter shows the last Input 1 value, with the fourth digit flashing.

7. Press

the

S/NT/GRS button to change the value of your digits.

8. Press

the

X/TARE button to scroll horizontally to the next digit.

9. Press

the

MENU button to store this value. The meter shows

.

10. Press the

X/TARE button. The meter shows the last value for Read 1.


Repeat steps 7, 8 and 9 until

,

and

have been displayed, verified, changed (if necessary) and

stored.

4.4 Using Reading Configuration

Refer to Table 6-1 for a summary list of menu configuration.

INPUT RANGE

R.2 = 4

R.2 = 3

R.2 =2

R.2 = 1

R.2 =0

0

to

100

mV

1.000 2.000 3.333 5.000 10.00

0

to

10

V

1.000 2.000 3.333 5.000 10.00

0

to

20

mA

1.000 2.000 3.333 5.000 10.00

±50

mV

1.000 1.000 1.667 2.500 5.000

±5

V

1.000 1.000 1.667 2.500 5.000

Advertising