Cooper Instruments & Systems DFI Infinity CS Economy Digital Indicator User Manual

Page 9

Advertising
background image

DFI INFINITY CS (V- M3598/N/0906)

6

CF 70

Table 2-2 Connector Description

Connector Description
TB1-1
TB1-2
TB1-3
TB1-4
TB1-5
TB1-6
TB1-7
TB1-8
TB1-9
TB1-10
TB1-11
TB1-12

Setpoint 1: Normally open (N.O.1) connection
Setpoint 1: Normally closed (N.C.1) connection
Setpoint 1: Common (COM1) connection
Setpoint 2: Normally open (N.O.2) connection
Setpoint 2: Normally closed (N.C.2) connection
Setpoint 2: Common (COM2) connection
AC line connection (no connections on DC-powered units)
AC neutral connection (+ Input on DC-powered units)
AC earth ground (DC-power return on DC-powered units)
Analog voltage output
Analog current output
Analog return

TB2-1
TB2-2
TB2-3
TB2-4
TB2-5
TB2-6
TB2-7
TB2-8

-E: Negative excitation connection from meter (5,10,12 V)
+E: Positive excitation connection from meter (5,10,12 V)
+20 mA connection for analog input
+R (Not used)
+24 V output connection
+S: Positive signal input
-S: Negative signal input and return for +20 mA or +24 V
-R (Not used)

TB5-1
TB5-2
TB5-3

Isolated Analog Voltage Output
Isolated Analog Current Output
Isolated Analog Output Return

J1 (1-2)

Remote tare connection with a momentary switch


The DIP switches are located at the S1 position (Refer to Figure 3-2). Use a small instrument such as a paper clip
to change the switches from open to closed. Table 2-3 lists DIP switch settings at the S1 position required to
complete the setup of your meter.

Table 2-3 DIP Switch Positions/Input Range & Excitation

Function

S1 DIP Switch Positions

C= Closed
O= Open

1 2 3 4 5 6 7 8

Settings for Excitation Voltage

Internal 5/10/12 excitation

C - - - - - - -

External 5/10/12 excitation

O - - - - O O -

Internal 12 Vdc Excitation

C - - - - O O -

Internal 10 Vdc Excitation

C - - - - C O -

Internal 5 Vdc Excitation

C - - - - C C -

Settings for Input Ranges

0-100 mV dc
±50 mV dc
±5 Vdc
0-10 Vdc
0-20 mA dc

-
-
-
-
-

O
O
C
C
O

C
C
O
O
C

O
O
O
O
C

O
C
C
O
O

-
-
-
-
-

-
-
-
-
-

O
O
C
C
O

The display must also be configured to the selected input type after setting the DIP switches (see Section