All models vent through right--side, See fig. 13), 58h d v – Carrier DIRECT VENT 4 58HDV User Manual

Page 20

Advertising
background image

20

EXH

A

U

ST

AI
R
F

L

O

W

INLE

T

IN

ON

OFF

VE

NT

Casing Grommet
Black Rubber

5

/

8

(15.9mm) CPVC

(Loose parts bag)

Drain Connector Black PVC

3

/

4

(19.1mm) PVC X

1

/

2

(12.7mm) CPVC
(Loose parts bag)

25--24--68

Single Pressure Switch Details

Dual Pressure Switch

Tee Trap White PVC
(loose parts bag)

2

(50.8mm)

PVC
Coupling

Barbed Coupling,

1

/

2

(12.7mm) OD

(loose parts bag)

Rotate
downward
5

° to 10°

NOTE: Built--in channel will
be angled 5

° to 10° also.

SIDE VIEW

Plastic Cap
Yellow or black

Vent Drain
& Clamps

On Some Models
ONLY

Either: The PVC Drain
Tee or a field supplied
2

(50.8mm) PVC Tee

Relief Tube
Black Rubber

3

/

16

″ 〈4.8mm) ID

Elbow Tubes (2) Black Rubber

1

/

2

(12.7mm) ID & Clamps

(loose parts bag)

Drain Tube
Corrugated

5

/

8

(15.9mm) ID &

Clamps

Drain Line Vent Tee

3

/

4

(18.1mm) PVC or

1

/

2

(12.7mm) CPVC (Field sup-
plied)

A07708

Fig. 13 -- All Models Vent Through Right Side

All Models Vent through Right--Side

(See Fig. 13)

Disconnect the black drain tube between the drain vent and the trap.
Rotate the inducer 180° for a right side vent after loosening the four

(4) inducer attachment screws. Reinstall and retighten the inducer
screws to 20 in. lb. (2.3Nm) torque.
Using the

1

/

2

″ (12.7mm) OD barbed coupling in the loose parts bag

connect together with the two short

1

/

2

″ (12.7mm) ID elbow tubes

and connect the lower discharge port of the vent drain to the trap.

Secure all connections with clamps.
Install the vent pipe grommet into the casing
Cut an appropriate length of 2″ (50.8mm) PVC pipe long enough

to exit the cabinet and connect the vent drain to either:

S

A 2″ (50.8mm) PVC coupling fastened onto the drain tee

Install tee trap into bottom section of tee.
Remove knockout from the side of the furnace casing where drain
tube will exit.
Install casing grommet black rubber [

5

/

8

″ (15.9mm) ID grommet --

in loose parts bag]

Install the

1

/

2

″ (12.7mm) CPVC street elbow on discharge of trap.

Install the black PVC tube connector [

3

/

4

″ (19.1mm) PVC x

1

/

2

(12.7mm) CPVC from loose parts bag] as shown in the illustration
above.
Cut the black drain tube [

5

/

8

″ (15.9mm) ID -- in loose parts bag] to

length to fit between trap and tube connector through grommet.
Clamp both ends of the drain tube using clamps provided.
Glue the CPVC street elbow to the trap using appropriate cleaner
and solvent cement.
Connect the tee trap and the main drain line exiting the casing as

shown in Fig. 13
NOTE:

It is recommended that all PVC piping and fitting

connections be fit up and inspected before final cementing. Both
the internal trap and the external tee trap must be primed
before operation.
Verify all condensate drain connections are
securely clamped. A coupling and clamps (in loose part bag) may
be installed as shown for future servicing of the vent system.