Caution, Warning, For single pipe installation – Carrier DIRECT VENT 4 58HDV User Manual

Page 8: Knock outs, Combustion & ventilation air, Outdoor combustion air method, Air openings and connecting ducts

Advertising
background image

8

If the furnace is to be suspended from the floor joists in a crawl
space or the rafters in an attic, it is necessary to use steel pipe straps

or an angle iron frame to rigidly attach the furnace to prevent
movement. These straps should be attached to the furnace bottom

side with sheet metal screws and to the rafters or joists with bolts.

The preferred method is to use an angle iron frame bolted to the
rafters or joists.
If the furnace is to be installed in a crawl space, consult local codes.
A suitable concrete pad or blocks are recommended for crawl space

installation on the ground.
NOTE: 6″ (152.4mm) bottom clearance required for condensate
trap.
24″ (609.6mm) inches between the front of the furnace and

adjacent construction or other appliances MUST be maintained for
service clearance. [30″ (762mm) inches is required to remove

furnace].
Keep all insulating materials clear from louvered door. Insulating
materials may be combustible.
The horizontal furnaces may be installed directly on combustible
wood flooring or supports as long as all required furnace clearances

are met. See Fig. 3.
This furnace MUST NOT be installed directly on carpeting or tile
or other combustible material other than wood flooring or supports.
For horizontal installation over a finished living space. A field
fabricated auxiliary drain pan with drain pipe is required to prevent

damage by overflow due to blocked condensate drain.

Knock Outs

A07702

Fig. 5 -- Hammer and Screwdriver used for Knockout

CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and

wear appropriate clothing, safety glasses and gloves when

handling parts and servicing furnaces.

CAUTION

!

Use a hammer and screwdriver to strike a sharp blow (See Fig. 5)
directly to the knockout tie points or use a hammer in the upper left

corner of the desired knockout. Remove any burrs and sharp edges.
NOTE: If a knockout does not come out after two sharp blows,
pull and snip as needed to remove the knockout.

COMBUSTION & VENTILATION

AIR

For Single Pipe Installation

CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury

or death.
Use methods described here to provide combustion and

ventilation air.

!

WARNING

Furnaces require ventilation openings to provide sufficient air for
proper combustion and ventilation of flue gases. All duct or

openings for supplying combustion and ventilation air must
comply with the gas codes, or in the absence of local codes, the

applicable national codes.
Combustion and ventilation air must be supplied in accordance

with one of the following:
NOTE:

The Combustion & Ventilation Air Section in this

document, uses tables and information from the ANSI
Z223.1/NFPA 54. For use in Canada, use CSA B149.1 for this
information.

1. Section 9.3, Air for Combustion and Ventilation, of the Na-

tional Fuel Gas Code, (NFGC), ANSI Z223.1--2006/NFPA

54--2006 in the U.S.,

2. Sections 8.2, 8.3, 8.5, 8.6, 8.7, and 8.8 of National Standard

of Canada, Natural Gas and Propane Installation Code
(NSCNGPIC), CSA B149.1--05 in Canada,

3. Applicable provisions of the local building code.

This furnace can NOT be common vented or connected to any type
B, BW or L vent or vent connector, nor to any portion of a

factory--built or masonry chimney. Multistory common venting is

NOT permitted. If this furnace is replacing a previously
common-vented furnace, it may be necessary to resize the existing

vent and chimney to prevent oversizing problems for the other
remaining appliance(s). See “Venting and Combustion Air Check”

in this section. This furnace MUST be vented to the outside.
When the installation is complete, check that all appliances have
adequate combustion air and are venting properly. See Venting And

Combustion Air Check in “Gas Vent Installation” Section in this
manual.

Outdoor Combustion Air Method

A space having less than 50 cubic feet per 1,000 BTUH input rating
for all gas appliances installed in the space requires outdoor air for

combustion and ventilation.

Air Openings and Connecting Ducts

1. Total input rating for all gas appliances in the space MUST

be considered when determining free area of openings.

2. Connect ducts or openings directly to the outdoors.
3. When screens are used to cover openings, the openings

MUST be no smaller than

1

/

4

″ (6.35 mm) mesh.

4. The minimum dimension of air ducts MUST NOT be less

than 3″ (76.2 mm).

5. When sizing a grille, louver, or screen use the free area of

opening. If free area is NOT stamped or marked on grill or

louver, assume a 20% free area for wood and 60% for metal.
Screens shall have a mesh size not smaller than

1

/

4

″ (6.35

mm) .

58H

D

V

Advertising