Dutchwest direct vent / natural vent gas heater, Venting runs, Venting requirements - natural vent only – Vermont Casting 2466 User Manual

Page 11: Termination clearances

Advertising
background image

11

Dutchwest Direct Vent / Natural Vent Gas Heater

30001935

Fig. 10 Termination clearances.

Venting Requirements - Natural Vent Only

FP567
NVBR/NVBC VENTING RUNS
11/12/97

Venting Runs

Horizontal Run (in feet)

Vertical Run (in feet)

(Measured from top of the unit before any elbow)

A: Vertical installations up to 36 feet (12m) in

height. Up to an 18 ft. horizontal vent run can be

installed within the vent system using a

maximum of two 90-degree elbows or four

45-degree elbows.

B: Vertical installations up to 36 feet (12m) in

height. Up to a 24 ft. horizontal vent run can be

installed within the vent system using a

maximum of two 45-degree elbows.

(Ratio = 2/3, Hor./Vert.)

= Acceptable venting configuration
= Unacceptable venting configuration

36
34
32
30
28
26
24
22
20
18
16
14
12
10

8
6
4
2

1 2 4 6 8 10 12 14 16 18 20 22 24

A

B

NOTE: When venting staight vertical, without any

elbow, a minimum of 8 ft. vertical is required

off the top of the stove.

FP567b

Fig. 11 Vent termination window - Natural Vent ONLY.

NOTE: When using the FSDHAG, the restrictor
plate supplied with the stove is not used.

Outside Corner

Inside Corner

Termination Clearances

Termination clearances for buildings with combustible and noncombustible exteriors.

G =

Combustible

6" (152 mm)

Noncombustible

2" (51 mm)

F =

Combustible

6" (152 mm)

Noncombustible

2" (51 mm)

G

Balcony -

with no side wall

M =
Combustible &
Noncombustible
12" (305 mm)

M

Balcony -

with perpendicular side wall

M = 24" (610 mm)
P = 20” (508 mm)

M

F

Alcove Applications*

C

D

C

E

V

V

Combustible &

Noncombustible

V

V

V

E

= Min. 6” (152 mm) for

non-vinyl sidewalls
Min. 12” (305 mm) for
vinyl sidewalls

O

= 8’ (2.4 m) Min.

O

P

584-15

No.

of Caps

D

Min.

C

Max.

1

3’ (.9 mm) 2 x D

Actual

2

6’ (1.8 m)

1 x D

Actual

3

9’ (2.7 m)

2/3 x D

Actual

4

12’ (3.7 m) 1/2 x D

Actual

D

Min.

= # of Termination caps x 3

C

Max.

= (2 / # termination caps) x D

Actual

*NOTE: Termination in an alcove space (spaces open only on one side and with an overhang) is permitted with the dimensions
specified for vinyl or non-vinyl siding and soffits. 1. There must be a 3’ (914 mm) minimum between termination caps. 2. All
mechanical air intakes within 10’ (1 m) of a termination cap must be a minimum of 3’ (914 mm) below the termination cap. 3. All
gravity air intakes within 3’ (914 mm) of a termination cap must be a minimum of 1’ (305 mm) below the termination cap.