Dutchwest direct vent / natural vent gas heater, Install the vent pipe – Vermont Casting 2466 User Manual

Page 18

Advertising
background image

18

Dutchwest Direct Vent / Natural Vent Gas Heater

30001935

8. Install appropriate pipe sections until the vent run

reaches above the flashing. The enlarged ends of
the vent sections always face downward.

9. Install the storm collar and seal around the joints.

(Fig. 31)

10. Add additional vent lengths to achieve the proper

overall height.

11. Apply cement to the inner and outer termination col-

lars and install the terminal cap.

ST222

vent thru ceiling

12/99

#7DVAIS

Attic

Insulation

Shield

#7DVFS

Firestop

In Upper

Floor

#7DVFS

Firestop in

Ceiling

Use Four 8d
Nails

ST222

Fig. 30 Install firestops and attic insulation shield.

ST221

vent thru roof

12/99

Storm Collar

Sealant

Upper

edge of

flange goes

under upper

shingles

Flashing

#7DVSKV

(A, B of F)

Roof Support

ST221

Fig. 31 Roof support and flashing.

Venting System Assembly - Natural Vent

General Information

The Dutchwest Heater is shipped from the factory as
a Direct Vent Heater. It may be converted to a Natural
Vent heater by installing the Model Z31D00 FSDHAG
Draft Hood Adapter.
The Dutchwest Heater is approved for installation as
a Natural Vent. CFM Direct Vent pipe could be used
directly after the Draft Hood Adapter up to the ceiling,
then B-vent pipe must be used. Do not mix types of
B-vent pipe; use components from one maker or the
other. Follow the vent component maker’s instructions
exactly. The heater will also accept standard or enam-
elled 7” (150mm) diameter pipe, around the Type B
venting, for decorative purposes only. (Fig. 32)
NOTE: The restrictor plate supplied with the stove
is not used for Natural Vent applications.

ST358

DW

Decorative

pipe around b-vent

5/15/03 djt

Decorative 7”
Pipe

4” B-vent

Pipe

Draft Hood

Adapter

CFM Direct Vent

System may be

used Draft Hood

up up to the ceiling

ST766

Fig. 32 Decorative 7” pipe may be fitted around the B-vent
pipe.

The Dutchwest stove, when installed as a Natural vent
heater, includes a vent safety switch. (Fig. 60, Page
32) Operating the stove when it is not connected to a
properly installed and maintained venting system, or
tampering with or disconnecting the vent safety switch,
can result in carbon monoxide (CO) poisoning and pos-
sible death.
For U.S. installations: The venting system must con-
form with local codes and/or the current National Fuel
Gas Code, ANSI Z22.1.
For Canadian installations: The venting system must
conform to the current CSA B149.1 installation code.

Install the Vent Pipe

Apply a bead of sealant around bottom end of inner
starter pipe (found in bag with logset) and attach to
stove. Apply a bead of sealant around top of inner
starter pipe and install the Z31D00 FSDHAG Draft
Hood according to Draft Hood instructions. (Fig. 33)