41

LCD Operation

|

Table 10. Alarms , Notices, and Events (Fortsetzung)

Name

Type

Description

Overload Warning

The total watts (W) reading for all three phases is
greater than the value configured as the overload
warning threshold. This warning indicates that the
current W reading is approaching the value set for the
overload alarm.

Generates an alarm and is logged in the Event Log.

Notice

Overload Alarm

The total watts (W) reading for all three phases is
greater than the value configured as the overload alarm
threshold.

Generates an alarm and is logged in the Event Log.

Alarm

Low Load Warning

The total watts (W) reading for all three phases is less
than the value configured as the low load warning
threshold. This warning indicates that the W reading is
approaching the value set for the low load alarm.

Generates an alarm and is logged in the Event Log.

Notice

Over Temperature Alarm

The temperature level reading is greater than the
maximum temperature threshold value. This alarm
clears when the temperature drops 5°C below the
Temperature High Alarm Level value setting.

Generates an alarm and is logged in the Event Log.

Alarm

Over Temperature Warning

The temperature level reading is greater than the
warning temperature threshold value. This alarm clears
when the temperature drops 5°C below the Temperature
High Warning Level value setting.

Generates an alarm and is logged in the Event Log.

Notice

Low Humidity Warning

The humidity level reading is less than the value
configured as the warning humidity threshold. This
alarm clears when the humidity rises 5% above the
Humidity Low Warning Level value setting.

Generates an alarm and is logged in the Event Log.

Notice

Low Humidity Alarm

The humidity level reading is less than the minimum
humidity threshold. This alarm clears when the
humidity rises 5% above the Humidity Low Alarm Level
value setting.

Generates an alarm and is logged in the Event Log.

Alarm

Contact 1 Active

The signal for Dry Contact 1 is active.

Generates an alarm and is logged in the Event Log.

Alarm

Contact 2 Active

The signal for Dry Contact 2 is active.

Generates an alarm and is logged in the Event Log.

Alarm

Meter IC Fault

Communication is lost.

Generates an alarm and is logged in the Event Log.

Alarm