Dell Metered PDU LCD User Manual

Page 84

Advertising
background image

84

|

Web Interface Operation

Table 28. Input Statistics (Fortsetzung)

Attribute

Description

Table

PDU Input Remaining Active Power (W)

Provides the watts capacity remaining.

NOTE: When the rPDU is in an overload state, this value
is always 0.

PDU Overload State

Present total watts (W) reading for all three phases is
compared to the value configured as the overload alarm
threshold. Either no threshold is triggered, or the
threshold has been surpassed.

Input Power
Statistics

PDU Input Peak Headroom Watts

(Values provided for Watts and Time)

Provides the remaining watts available to support the
load at peak demand. Provides a time and date stamp of
the most recent data update. Click Reset to clear this
value to the maximum value for this model and reset the
time to the present time.

PDU Input Peak Consumption Watts

(Values provided for Watts and Time)

Provides the peak power demand on the rPDU. Provides
a time and date stamp of the most recent data update.
Click Reset to clear this value to zero (0) and reset the
time to the present time.

PDU Input Cumulative kWh

(Values provided for Watts and Time)

Provides the total kWh usage. Provides a time and date
stamp of the most recent data update.
NOTE: This value accumulates. If this value reaches the
maximum value for a 32-bit number, do not reset.
Click Reset to clear this value to zero (0) and reset the
time to the present time.

Input Thresholds

Phase 1 Current Thresholds (A)

Low Warning: Causes an alarm when the input current
amperage (A) reading falls below the low warning
threshold value displayed in the table.

High Warning: Causes an alarm when the input current
amperage (A) reading exceeds the high warning
threshold value displayed in the table.

High Critical: Causes an alarm when the input current
amperage (A) reading exceeds the high critical threshold
value displayed in the table.

Phase 2 Current Thresholds (A)

Low Warning: Causes an alarm when the input current
amperage (A) reading falls below the low warning
threshold value displayed in the table.

High Warning: Causes an alarm when the input current
amperage (A) reading exceeds the high warning
threshold value displayed in the table.

High Critical: Causes an alarm when the input current
amperage (A) reading exceeds the high critical threshold
value displayed in the table.

Phase 3 Current Thresholds (A)

Low Warning: Causes an alarm when the input current
amperage (A) reading falls below the low warning
threshold value displayed in the table.

High Warning: Causes an alarm when the input current
amperage (A) reading exceeds the high warning
threshold value displayed in the table.