Dell Metered PDU LCD User Manual

Page 46

Advertising
background image

46

|

LCD Operation

Table 11. Settings (Continued)

Setting Option

Default Setting

Available Settings

Settings
Submenu

L2 Settings

L2 Over Current Warning Level [0.0A]...[48.0A] *

[0.0A]...[32.0A] **

[0.0A]...[16.0A] ***

An input current amperage (A) reading greater
than this value causes a warning to generate.
This warning indicates that the current A
reading has risen to an unacceptable level.

38.4A

25.6A

12.8A

L2 Over Current Alarm Level

[0.0A]...[48.0A] *

[0.0A]...[32.0A] **

[0.0A]...[16.0A] ***

An input current amperage (A) reading greater
than this value causes a over current alarm to
generate.

48.0A

32.0A

16.0A

L2 Low Current Warning Level

[0.0A]...[48.0A] *

[0.0A]...[32.0A] **

[0.0A]...[16.0A] ***

An input current amperage (A) reading less
than this value causes a warning to generate.
This warning indicates that the current A
reading is reduced to an unacceptable level.

0.0A

0.0A

0.0A

L3 Settings

L3 Over Current Warning Level [0.0A]...[48.0A] *

[0.0A]...[32.0A] **

[0.0A]...[16.0A] ***

An input current amperage (A) reading greater
than this value causes a warning to generate.
This warning indicates that the current A
reading has risen to an unacceptable level.

38.4A

25.6A

12.8A

L3 Over Current Alarm Level

[0.0A]...[48.0A] *

[0.0A]...[32.0A] **

[0.0A]...[16.0A] ***

An input current amperage (A) reading greater
than this value causes an over current alarm to
generate.

48.0A

32.0A

16.0A

L3 Low Current Warning Level

[0.0A]...[48.0A] *

[0.0A]...[32.0A] **

[0.0A]...[16.0A] ***

An input current amperage (A) reading less
than this value causes a warning to generate.
This warning indicates that the current A
reading is reduced to an unacceptable level.

0.0A

0.0A

0.0A

* DELLM0001, DELLM001A, DELLM0004, DELLM004A, DELLM0006

** DELLM0002, DELLM0005, DELLM0007

*** DELLM0003

NOTE:

For Delta models, L1 represents L1-L3 data, L2 represents L1-L2 data, and L3 represents L2-L3 data.

Advertising