Managing environment sensors – Dell Metered PDU LCD User Manual

Page 86

Advertising
background image

86

|

Web Interface Operation

The meter bar colors on the Input page represent the following:

S

Blue – The current reading for L1, L2, or L3 is below the low current warning threshold value that displays
in the Low warning field, or the overall rPDU input wattage reading is below the load threshold value in the
Low warning field.

S

Green – The current reading is within the range of tolerance and no threshold has been triggered.

S

Yellow – The current reading for L1, L2, or L3 is above the current warning threshold value that displays in
the High warning field, or the overall rPDU input wattage reading is above the load threshold value in the
High warning field.

S

Red – The current reading for L1, L2, or L3 is above the current critical alarm threshold value that displays
in the High critical field, or the overall rPDU input wattage reading is above the load threshold value in the
High critical field.

Managing Environment Sensors

To view readings or change warning thresholds for environment sensors:

1

From the

Power Management

menu, click

Environment

. The Environment page displays.

2

Review the present values for all sensors connected to the rPDU (see Table 29 and Figure 41).

NOTE:

If a sensor is not connected to the rPDU, a “Non-active” value displays.

NOTE:

If you change any sensor threshold values, you must click Save to save your changes (see Table 29).

3

This procedure is completed.

Table 29 describes the attributes in the Environment tables.

Table 29. Environment

Table

Attribute

Description

Present Values

Temperature

(°C)

Displays the temperature in °C on the Temperature
screen. A meter bar provides a visual representation of
the reading.

Humidity (%)

Displays the humidity percentage on the Humidity
screen. A meter bar provides a visual representation of
the reading.

Over Temperature State

The current temperature compared to the value
configured as the temperature threshold. Either no
threshold is triggered, or the threshold has been
surpassed.

Under Humidity State

The current humidity compared to the value configured
as the under-humidity threshold. Either no threshold is
triggered, or the threshold has been surpassed.

Dry Contact 1 State

The present state of dry contact 1. Either the dry contact
is Normally Closed, Normally Open, or Non-active.

Dry Contact 2 State

The present state of dry contact 2. Either the dry contact
is Normally Closed, Normally Open, or Non-active.

Sensor Name

Temperature

& Humidity Sensor

The user-defined sensor name.

Dry Contact 1

The user-defined dry contact 1 sensor name.

Dry Contact 2

The user-defined dry contact 2 sensor name.