Dell PowerVault DR4100 User Manual

Page 103

Advertising
background image

Environmental

Conductive Dust

NOTE: Applies to data center and non-data center
environments.

Air must be free of conductive dust, zinc whiskers, or
other conductive particles.

Corrosive Dust

NOTE: Applies to data center and non-data center
environments.

Air must be free of corrosive dust.

Residual dust present in the air must have a

deliquescent point less than 60% relative

humidity.

Gaseous Contamination

NOTE: Maximum corrosive contaminant levels measured at ≤50% relative humidity.

Copper Coupon Corrosion Rate

<300 Å/month per Class G1 as defined by ANSI/
ISA71.04-1985.

Silver Coupon Corrosion Rate

<200 Å/month as defined by AHSRAE TC9.9.

103

Advertising