Dell UPS 10000R User Manual

Page 70

Advertising
background image

70

|

MIB Objects

Table 15. Product Physical Group Variables (continued)

Trap Name, Description, and Relative XML Object Path

Trap Level

Trap

trapBypassFrequencyOutOfRange

Bypass under or over frequency

UPS.PowerConverter.Input[2].PresentStatus.FrequencyOutOfRange = 1

5

2

trapBypassFrequencyOutOfRangeOk

Bypass under or over frequency ok

UPS.PowerConverter.Input[2].PresentStatus.FrequencyOutOfRange = 0

6

1

trapOnBuck

On Buck / Input Voltage Reducer

UPS.PowerConverter.Input[1].PresentStatus.Buck = 1

7

1

trapReturnFromBuck

Return from Buck

UPS.PowerConverter.Input[1].PresentStatus.Buck = 0

8

1

trapOnBoost

On Boost / Input Voltage Booster

UPS.PowerConverter.Input[1].PresentStatus.Boost = 1

9

1

trapReturnFromBoost

Return from Boost

UPS.PowerConverter.Input[1].PresentStatus.Boost = 0

10

1

trapInputOverVoltage

Input AC over voltage

UPS.PowerConverter.Input[1].PresentStatus.VoltageTooHigh = 1

11

2

trapInputOverVoltageOk

Input AC over voltage ok

UPS.PowerConverter.Input[1].PresentStatus.VoltageTooHigh = 0

12

1

trapInputUnderVoltage

Input AC under voltage

UPS.PowerConverter.Input[1].PresentStatus.VoltageTooLow = 1

13

2

trapInputUnderVoltageOk

Input AC under voltage ok

UPS.PowerConverter.Input[1].PresentStatus.VoltageTooLow = 0

14

1

trapInputFrequencyOutOfRange

Input under or over frequency

UPS.PowerConverter.Input[1].PresentStatus.FrequencyOutOfRange = 1

15

2

Advertising