Dell UPS 10000R User Manual

Page 71

Advertising
background image

71

MIB Objects

|

Table 15. Product Physical Group Variables (continued)

Trap Name, Description, and Relative XML Object Path

Trap Level

Trap

trapInputFrequencyOutOfRangeOk

Input under or over frequency ok

UPS.PowerConverter.Input[1].PresentStatus.FrequencyOutOfRange = 0

16

1

trapRemoteEmergencyPowerOff

Remote emergency power off

UPS.PowerSummary.PresentStatus.EmergencyStop = 1

17

2

trapReturnFromEmergencyPowerOff

Return from remote emergency power off

UPS.PowerSummary.PresentStatus.EmergencyStop = 0

18

1

trapOutputOverload

Output overload

UPS.PowerSummary.PresentStatus.Overload = 1

19

2

trapOutputOverloadOk

Output overload ok

UPS.PowerSummary.PresentStatus.Overload = 0

20

1

trapLevel2Overload

Level 2 overload

UPS.PowerConverter.Output.Overload[1].PresentStatus.OverThreshold = 1

21

2

trapLevel2OverloadOk

Level 2 overload ok

UPS.PowerConverter.Output.Overload[1].PresentStatus.OverThreshold = 0

22

1

trapLevel3Overload

Level 3 overload

UPS.PowerConverter.Output.Overload[2].PresentStatus.OverThreshold = 1

23

3

trapLevel3OverloadOk

Level 3 overload ok

UPS.PowerConverter.Output.Overload[2].PresentStatus.OverThreshold = 0

24

1

trapPosDCLinkOverVoltage

Positive DC link over voltage (applies only to double-conversion models)

UPS.PowerConverter.Rectifier.PresentStatus.HighPositiveDCBusVoltage = 1

25

2

trapPosDCLinkOverVoltageOk

Positive DC link over voltage ok

UPS.PowerConverter.Rectifier.PresentStatus.HighPositiveDCBusVoltage = 0

26

1

Advertising