MIB Objects

Table 15. Product Physical Group Variables (continued)

Trap Name, Description, and Relative XML Object Path

Trap Level

Trap

trapPosDCLinkUnderVoltage

Positive DC link under voltage (applies only to double-conversion models)

UPS.PowerConverter.Rectifier.PresentStatus.LowPositiveDCBusVoltage = 1

27

2

trapPosDCLinkUnderVoltageOk

Positive DC link under voltage ok

UPS.PowerConverter.Rectifier.PresentStatus.LowPositiveDCBusVoltage = 0

28

1

trapNegDCLinkOverVoltage

Negative DC link over voltage (applies only to double-conversion models)

UPS.PowerConverter.Rectifier.PresentStatus.HighNegativeDCBusVoltage = 1

29

2

trapNegDCLinkOverVoltageOk

Negative DC link over voltage ok

UPS.PowerConverter.Rectifier.PresentStatus.HighNegativeDCBusVoltage = 0

30

1

trapNegDCLinkUnderVoltage

Negative DC link under voltage (applies only to double-conversion models)

UPS.PowerConverter.Rectifier.PresentStatus.LowNegativeDCBusVoltage = 1

31

2

trapNegDCLinkUnderVoltageOk

Negative DC link under voltage ok

UPS.PowerConverter.Rectifier.PresentStatus.LowNegativeDCBusVoltage = 0

32

1

trapRectifierFault

Rectifier fault (applies only to double-conversion models)

UPS.PowerConverter.Rectifier.PresentStatus.InternalFailure = 1

33

3

trapRectifierOk

Rectifier ok

UPS.PowerConverter.Rectifier.PresentStatus.InternalFailure = 0

34

1

trapInverterFault

Inverter fault (applies only to double-conversion models)

UPS.PowerConverter.Inverter.PresentStatus.InternalFailure = 1

35

3

trapInverterOk

Inverter ok

UPS.PowerConverter.Inverter.PresentStatus.InternalFailure = 0

36

1

trapChargerFailure

Charger failure

UPS.BatterySystem.Charger.PresentStatus.InternalFailure = 1

37

3