Actuation and reset, Setpoint adjustment, Testing – KMC Controls CTE-3007 User Manual

Page 2: Accessories, Maintenance, Specifications, Important notices, Specifications 2 important notices 2, Specifications maintenance

Advertising
background image

CTE-3016/3017/3026/3027

2

Installation Guide

© 2010 KMC Controls, Inc.

717-019-24B

KMC Controls, Inc.

19476 Industrial Drive

New Paris, IN 46553

574.831.5250

www.kmccontrols.com; [email protected]

Accessories

HMO-4523

Capillary Clip (ordering about 5

clips per unit is recommended)

Important Notices

The material in this document is for information

purposes only. The contents and the product it

describes are subject to change without notice. KMC

Controls, Inc. makes no representations or warran-

ties with respect to this document. In no event shall

KMC Controls, Inc. be liable for any damages, direct

or incidental, arising out of or related to the use of

this document.

Specifications

Maintenance

No routine maintenance is required. Each compo-

nent is designed for dependable, long-term reliabil-

ity, and performance. Careful installation will also

ensure long-term reliability and performance.

Setpoint Adjustment

The setpoint is the temperature at which connection

“1–4” opens as the unit senses a fall in temperature.

To adjust the setpoint:
• Turn the range adjustment screw CW to decrease

the setpoint.

• Turn the range adjustment screw CCW to

increase the setpoint.

Testing

A manual test lever located under the cover (below

the indicator) allows the unit to be manually actu-

ated (with a screwdriver) during system tests.

Actuation and Reset

Terminal 1 is the “common” terminal, 4 is NC

(above setpoint), and 2 is NO. When the sensed

temperature falls below setpoint, connection “1–4”

opens and connection “1–2” closes (see diagram

below). The switch latches in this position until the

sensed temperature rises 5° F (3° C) above setpoint

and the controller is reset either (depending on the

model) automatically or manually by depressing the

reset button located in the top of the controller case.
The controller cannot be manually reset until the

sensed temperature is at least 5° F (3° C) above

setpoint.

Common

Normally Open (Closes on Low Temp.)

Normally Closed (Opens on Low Temp.)

Range

35 to 68° F (1.7 to 20° C)

Differential

4.5° F fixed (2.5° C)

Switch Action

SPDT, snap-acting

Element

3/32" (2.4 mm) diameter,

20-foot (607 cm) length,

vapor-filled, tin-plated copper

capillary, max. temperature

300° F (149° C)

Electrical Ratings

Inductive

24 FLA (Full Load Amperes)

@ 120/240 VAC

144 LRA (Locked Rotor

Amperes) @ 120/240 VAC

2 HP @ 120 VAC, 3 HP @ 240

VAC

Pilot Duty

720 VA max. @ 120 to 600 VAC,

144 VA max. @ 24 VAC

Approvals

CUL US Listed, CE Compliant,

RoHs compliant

Weight

1.0 lbs. (0.45 kg)

Materials

Plated steel case, plastic cover

Mounting

Surface mount with capillary

installed in horizontal serpen-

tine pattern

Temperature Limits

Operating

–60 to 160° F (–51 to 71° C)

Shipping

–60 to 160° F (–51 to 71° C)

NOTE: See the CTE-3006/3007 Data Sheet (717-035-

24) for more information.