Dell PowerVault 775N (Rackmount NAS Appliance) User Manual
Page 25
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".
Figure 1-14. Two-Post, Open-Frame Relay Rack Wide-Hole Spacing
44 mm (1.75 inches) (1 U)
c —
‘c-r
1.7
c
12.7 mm (0.5 inch)
31.7 mm (1.25 inches)
To mark the rack, perform the following steps:
1
Place a mark on the rack’s front vertical rails where you want to locate the bottom of
the system you are installing in the two-post rack.
The bottom of each 1-U space is at the middle of the narrowest metal area between
holes.
^ NOTE:
If your rack has wide-hole spacing, go to step 3.
2
Place a mark 88 mm (5.5 inches) above the original mark you made (or count up six
holes in a rack with universal-hole spacing (see Figure 1-15).
Each 1-U (44 mm, or 1.75 inches) of vertical space on a rack with universal-hole
spacing has three holes with center-to-center spacing between holes (beginning at the
top of a 1-U space) of 0.625, 0.625, and 0.5 inches (see Figure 1-15).
^ NOTE:
If your rack has universal-hole spacing, you have completed the procedure for
marking the rack.
3
Place a mark 88 mm (5.5 inches) above the original mark you made (or count up to the
fourth hole in the rack with wide-hole spacing (see Figure 1-14).
Each 1-U (44 mm, or 1.75 inches) of vertical space on a rack with wide-hole spacing
has two holes with center-to-center spacing between holes (beginning at the top of a
1-U space) of 51.7 mm (1.25 inches) (see Figure 1-14).
R a c k I n s t a l l a t i o n G u i d e |
1-21