Table 4 — Electrical Data — 50EJ,EK,EW,EY024-048

UNIT

SIZE

NOMINAL
VOLTAGE

(3 Ph 60 Hz)

VOLTAGE

RANGE

COMPRESSOR

OFM

IFM

POWER

EXHAUST

ELECTRIC

HEAT*

POWER SUPPLY

No. 1

No. 2

Min

Max

RLA

LRA

RLA

LRA

Qty

Hp

FLA (ea)

Hp

FLA

FLA

LRA

kW

FLA

MCA

MOCP†

024

208/230

187

254

39.1

228

25.6

160

2

1

5.3

5

16.7/

15.2

101.8/100.3

125/125

23.6

41.6

125.4/123.9

150/150

29/36

75.1/ 86.6

114.7/127.3

125/150

23.6

41.6

29/36

75.1/ 86.6

144.2/156.8

150/175

59/72

150.1/173.2

171.0/192.2

200/225

23.6

41.6

59/72

150.1/173.2

200.5/221.7

225/225

10

30.8/

28.0

115.9/113.1

150/150

23.6

41.6

139.5/136.7

175/175

29/36

75.1/ 86.6

132.3/143.3

150/150

23.6

41.6

29/36

75.1/ 86.6

161.8/172.8

175/175

59/72

150.1/173.2

188.6/208.2

220/225

23.6

41.6

59/72

150.1/173.2

218.1/237.7

250/250

15

46.2/

42.0

131.3/127.1

150/150

23.6

41.6

154.9/150.7

175/175

29/36

75.1/ 86.6

151.6/160.8

175/175

23.6

41.6

29/36

75.1/ 86.6

181.1/190.3

200/200

59/72

150.1/173.2

207.9/225.7

250/250

23.6

41.6

59/72

150.1/173.2

237.4/255.2

275/275

460

414

508

19.9

114

11.5

80

2

1

2.7

5

7.6

49.4

60

12.6

23.6

62.0

80

36

43.3

63.6

70

12.6

23.6

36

43.3

79.4

80

72

86.6

96.1

110

12.6

23.6

72

86.6

111.9

125

10

14

55.8

70

12.6

23.6

68.4

80

36

43.3

71.6

80

12.6

23.6

36

43.3

87.4

90

72

86.6

104.1

110

12.6

23.6

72

86.6

119.9

125

15

21

62.8

80

12.6

23.6

75.4

90

36

43.3

80.4

90

12.6

23.6

36

43.3

96.1

100

72

86.6

112.9

125

12.6

23.6

72

86.6

128.6

150

575

518

632

16.0

91

9.6

64

2

1

2.4

5

6.1

40.5

50

12.6

23.6

53.1

60

36

34.6

50.9

60

12.6

23.6

36

34.6

66.7

70

72

69.3

76.9

80

12.6

23.6

72

69.3

92.7

100

10

11

45.4

60

12.6

23.6

58.0

70

36

34.6

57.1

60

12.6

23.6

36

34.6

72.8

80

72

69.3

83.0

90

12.6

23.6

72

69.3

98.8

100

15

17

51.4

60

12.6

23.6

64.0

80

36

34.6

64.6

70

12.6

23.6

36

34.6

80.3

90

72

69.3

90.5

100

12.6

23.6

72

69.3

106.3

110

LEGEND

FLA

Full Load Amps

HACR

Heating, Air Conditioning and Refrigeration

IFM

Indoor (Evaporator) Fan Motor

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection
NEC

National Electrical Code

OFM

Outdoor (Condenser) Fan Motor

RLA

Rated Load Amps

*Heater capacity (kW) is based on heater voltage of 208 v, 240 v, 480 v, and 575 v.

If power distribution voltage to unit varies from rated heater voltage, heater kW will
vary accordingly.

†Fuse or HACR circuit breaker.

NOTES:
1. In compliance with NEC requirements for multimotor and combination load equip-

ment (refer to NEC Articles 430 and 440), the overcurrent protective device for the
unit shall be fuse or HACR breaker. The Canadian units may be fuse or circuit
breaker.

2. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater than
2%. Use the following formula to determine the percent of voltage imbalance.

max voltage deviation from average voltage

% Voltage Imbalance = 100 x

average voltage

EXAMPLE: Supply voltage is 460-3-60.

AB = 452 v
BC = 464 v
AC = 455 v

452 + 464 + 455

Average Voltage =

3

1371

=

3

= 457

Determine maximum deviation from average voltage.

(AB) 457 − 452 = 5 v
(BC) 464 − 457 = 7 v
(AC) 457 − 455 = 2 v

Maximum deviation is 7 v.

Determine percent of voltage imbalance.

7

% Voltage Imbalance = 100 x

457

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maximum
allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%,
contact your local electric utility company immediately.

3. MCA calculation for units with electric heaters over 50 kW = (1.25 x IFM amps) +

(1.00 x heater FLA).

17