NOTES:
1. Weights include economizer (Std)

2.

Center of gravity.

3. Do not locate adjacent units with discharge facing economizer inlet.

Minimum clearances to be:

Adjacent Units: 15

Ј

-0

Љ

Top of Units: No overhang
Condenser Coil: 4

Ј

-0

Љ

Economizer Side: 6

Ј

-0

Љ

Filter Access Side: 10

Ј

-0

Љ

(for removal of evaporator coil)

4. For smaller service and operational clearances, contact Carrier

Application Engineering department.

5. Dimensions are in inches. Dimensions in [

] are in millimeters.

6. For units equipped with electric heat, a field-supplied 90° elbow must

be installed in the supply ductwork below the unit discharge.

7. For side-supply/return applications, a single return and supply duct-

work connection is recommended for covering both return and both
supply air openings.

UNIT SIZE

50E

OPERATING

WEIGHT

(lb)

A

B

CORNER WEIGHT

(lb)

ft-in.

ft-in.

1

2

3

4

W038

4282

7-7

5

16

3-10

1

2

961 858 1162 1302

W/Y044

4508

7-3

13

16

3-11

1

2

973 868 1258 1409

W048

4795

7-2

3

16

3-10

3

32

1007 915 1368 1505

Fig. 6 — Base Unit Dimensions, 50EW038-048 and 50EY044

LEGEND

VFD — Variable Frequency Drive

7